VACON® 100 FLOW
Application Guide
Troubleshooting
•
Check the control panel connection and the control panel cable if you have it.
12.3.103 Fault Code 53, ID 1053 - Fieldbus Communication Fault
Cause
•
The data connection between the fieldbus master and the fieldbus board is defective.
Troubleshooting
•
Check the installation and fieldbus master.
12.3.104 Fault Code 53, ID 1054 - Redundant Switchover
Cause
•
The data connection between controlling fieldbus and the drive has timed out. Redundant control has changed the controlling
fieldbus connection.
Troubleshooting
•
Check the installation and the communication cables.
12.3.105 Fault Code 53, ID 1055 - Redundant Timeout
Cause
•
The data connection between controlling fieldbus protocols and the drive has timed out.
Troubleshooting
•
Check the installation and the communication cables.
12.3.106 Fault Code 54, ID 1354 - Slot A fault
Cause
•
A defective option board or slot.
Troubleshooting
•
Check the board and the slot.
•
Ask for instructions from your nearest distributor.
12.3.107 Fault Code 54, ID 1454 - Slot B fault
Cause
•
A defective option board or slot.
Troubleshooting
•
Check the board and the slot.
•
Ask for instructions from your nearest distributor.
12.3.108 Fault Code 54, ID 1554 - Slot C fault
Cause
•
A defective option board or slot.
Troubleshooting
•
Check the board and the slot.
•
Ask for instructions from your nearest distributor.
12.3.109 Fault Code 54, ID 1654 - Slot D fault
Cause
•
A defective option board or slot.
Troubleshooting
•
Check the board and the slot.
•
Ask for instructions from your nearest distributor.
Danfoss A/S © 2023.08
Fault Tracing
AB298035655957en-000201 / DPD01083 | 313