11.24.8.7 (ID 3551) Vibration Min Factor
Location in the menu: P3.24.4.2.2
Use this parameter to set the min factor in the threshold value. If the threshold value is zero, the min factor is not used.
11.24.8.8 (ID 3552) Vibration Max Factor
Location in the menu: P3.24.4.2.3
Use this parameter to set the max factor in the threshold value. If the threshold value is zero, the max factor is not used.
11.24.8.9 (ID 3553) Vibration Std Factor
Location in the menu: P3.24.4.2.4
Use this parameter to set the std factor in the threshold value. If the threshold value is zero, the std factor is not used.
11.24.8.10 (ID 3554) Vibration Interpolation Type
Location in the menu: P3.24.4.2.5
Use this parameter to select interpolation type for the notification threshold values across frequency points.
11.24.8.11 (ID 3567) Load Mean Factor
Location in the menu: P3.24.5.1.1
Use this parameter to set the mean factor in the threshold value. If the threshold value is zero, the mean factor is not used.
11.24.8.12 (ID 3568) Load Min Factor
Location in the menu: P3.24.5.1.2
Use this parameter to set the min factor in the threshold value. If the threshold value is zero, the min factor is not used.
11.24.8.13 (ID 3569) Load Max Factor
Location in the menu: P3.24.5.1.3
Use this parameter to set the max factor in the threshold value. If the threshold value is zero, the max factor is not used.
11.24.8.14 (ID 3570) Load Std Factor
Location in the menu: P3.24.5.1.4
Use this parameter to set the std factor in the threshold value. If the threshold value is zero, the std factor is not used.
11.24.8.15 (ID 3571) Load Interpolation Type
Location in the menu: P3.24.5.1.5
Use this parameter to select interpolation type for the notification threshold values across frequency points.
11.24.9 Warning and Alarm/Fault Stages
Each of the three detection levels (Warning S1, Warning S2, Alarm/Fault) has a configurable timer associated that delays the re-
sponse. The timing principle is like an electrical fuse where the response time is long for low levels and it is short for high levels.
11.24.9.1 (ID 3516) Current Warning S1 Mode
Location in the menu: P3.24.3.3.2.1
Use this parameter to select the warning S1 mode which is used for calculating warning S1 notification threshold.
Selection number
Selection name
0
Absolute
1
Offset
2
Factor
284 | Danfoss A/S © 2023.08
Description
Absolute value is considered as threshold
Calculates threshold as sum of the computed baseline data and the offset values
Calculates threshold as baseline data factor
Parameter Descriptions
AB298035655957en-000201 / DPD01083