VACON® 100 FLOW
Application Guide
12.3.123 Fault Code 68, ID 1303 - Maintenance Counter 2 Alarm
Cause
The value of the maintenance counter is higher than the alarm limit.
Troubleshooting
Do the necessary maintenance.
Reset the counter. See parameter B3.16.4 or P3.5.1.40.
12.3.124 Fault Code 68, ID 1304 - Maintenance Counter 2 Fault
Cause
The value of the maintenance counter is higher than the fault limit.
Troubleshooting
Do the necessary maintenance.
Reset the counter. See parameter B3.16.4 or P3.5.1.40.
12.3.125 Fault Code 69, ID 1310 - Fieldbus Mapping Error
Cause
The ID number that is used to map the values to Fieldbus Process Data Out is not valid.
Troubleshooting
Check the parameters in the Fieldbus Data menu.
12.3.126 Fault Code 69, ID 1311 - Fieldbus Mapping Error
Cause
It is not possible to convert 1 or more values for Fieldbus Process Data Out.
The type of the value is undefined.
Troubleshooting
Check the parameters in the Fieldbus Data menu.
12.3.127 Fault Code 69, ID 1312 - Fieldbus Mapping Error
Cause
There is an overflow when the values for Fieldbus Process Data Out (16-bit) are mapped and converted.
Troubleshooting
Check the parameters in the Fieldbus Data menu.
12.3.128 Fault Code 70, ID 1120 - BaselineRun Failed
Cause
There was a failure during the baseline run.
Troubleshooting
Do a check of the parameters in the baseline run settings.
12.3.129 Fault Code 70, ID 1133 - Online Run Interrupted
Cause
Online run interrupted before completion.
Troubleshooting
Restart baseline run.
12.3.130 Fault Code 71, ID 1121 - Stator Winding: Current Warning S1
Cause
Current unbalance has exceeded the detection high limit. Early fault detected in motor.
316 | Danfoss A/S © 2023.08
Fault Tracing
AB298035655957en-000201 / DPD01083