VACON® 100 FLOW
Application Guide
Parameter Descriptions
Use this parameter to set the time that the output frequency of the drive and the error value of the PID controller must stay in the
hysteresis areas before the SNDD function becomes active.
11.15.10.5 (ID 1669) SNND Actual Add
Location in the menu: P3.13.10.5
Use this parameter to set the value that is added to the actual value of the PID feedback for a short time when the SNDD function is
active.
11.15.11 Multi-setpoint
11.15.11.1 (ID 15560) Multi-setpoint 0
Location in the menu: P3.13.12.1
Use this parameter to set the preset PID setpoint value when the Multi-setpoint function is used. Make the selection of the multi-
setpoint with the digital input signals.
11.15.11.2 (ID 15561) Multi-setpoint 1
Location in the menu: P3.13.12.2
Use this parameter to set the preset PID setpoint value when the Multi-setpoint function is used. Make the selection of the multi-
setpoint with the digital input signals.
11.15.11.3 (ID 15562) Multi-setpoint 2
Location in the menu: P3.13.12.3
Use this parameter to set the preset PID setpoint value when the Multi-setpoint function is used. Make the selection of the multi-
setpoint with the digital input signals.
11.15.11.4 (ID 15563) Multi-setpoint 3
Location in the menu: P3.13.12.4
Use this parameter to set the preset PID setpoint value when the Multi-setpoint function is used. Make the selection of the multi-
setpoint with the digital input signals.
11.15.11.5 (ID 15564) Multi-setpoint 4
Location in the menu: P3.13.12.5
Use this parameter to set the preset PID setpoint value when the Multi-setpoint function is used. Make the selection of the multi-
setpoint with the digital input signals.
11.15.11.6 (ID 15565) Multi-setpoint 5
Location in the menu: P3.13.12.6
Use this parameter to set the preset PID setpoint value when the Multi-setpoint function is used. Make the selection of the multi-
setpoint with the digital input signals.
11.15.11.7 (ID 15566) Multi-setpoint 6
Location in the menu: P3.13.12.7
Use this parameter to set the preset PID setpoint value when the Multi-setpoint function is used. Make the selection of the multi-
setpoint with the digital input signals.
11.15.11.8 (ID 15567) Multi-setpoint 7
Location in the menu: P3.13.12.8
Use this parameter to set the preset PID setpoint value when the Multi-setpoint function is used. Make the selection of the multi-
setpoint with the digital input signals.
11.15.11.9 (ID 15569) Multi-setpoint 9
Location in the menu: P3.13.12.10
Use this parameter to set the preset PID setpoint value when the Multi-setpoint function is used. Make the selection of the multi-
setpoint with the digital input signals.
Danfoss A/S © 2023.08
AB298035655957en-000201 / DPD01083 | 251