11.7.4.5 (ID 424) Control Signal 2 B
Location in the menu: P3.5.1.5
Use this parameter to select the digital input signal (Control Signal 2) that starts and stops the drive when the control place is I/O B.
11.7.4.6 (ID 435) Control Signal 3 B
Location in the menu: P3.5.1.6
Use this parameter to select the digital input signal (Control Signal 3) that starts and stops the drive when the control place is I/O B.
11.7.4.7 (ID 425) I/O B Control Force
Location in the menu: P3.5.1.7
Use this parameter to select the digital input signal that switches the control place from I/O A to I/O B.
11.7.4.8 (ID 343) I/O B Reference Force
Location in the menu: P3.5.1.8
Use this parameter to select the digital input signal that switches the frequency reference source from I/O A to I/O B.
11.7.4.9 (ID 411) Fieldbus Control Force
Location in the menu: P3.5.1.9
Use this parameter to select the digital input signal that switches the control place and the frequency reference source to Fieldbus
(from I/O A, I/O B or Local control).
11.7.4.10 (ID 410) Keypad Control Force
Location in the menu: P3.5.1.10
Use this parameter to select the digital input signal that switches the control place and the frequency reference source to Keypad
(from any control place).
11.7.4.11 (ID 405) External Fault Close
Location in the menu: P3.5.1.11
Use this parameter to select the digital input signal that activates an external fault.
11.7.4.12 (ID 406) External Fault Open
Location in the menu: P3.5.1.12
Use this parameter to select the digital input signal that activates an external fault.
11.7.4.13 (ID 414) Fault Reset Close
Location in the menu: P3.5.1.13
Use this parameter to select the digital input signal that resets all active faults. Active faults are reset when the state of the digital
input changes from open to closed (rising edge).
11.7.4.14 (ID 213) Fault Reset Open
Location in the menu: P3.5.1.14
Use this parameter to select the digital input signal that resets all active faults. Active faults are reset when the state of the digital
input changes from closed to open (falling edge).
11.7.4.15 (ID 407) Run Enable
Location in the menu: P3.5.1.15
Use this parameter to select the digital input signal that sets the drive to Ready state. When the contact is OPEN, the start of the
motor is disabled. When the contact is CLOSED, the start of the motor is enabled.
The state of the drive remains in 'Not Ready' if the state of this signal is 'opened'. If the Run Enable signal is used for stopping the
drive, the drive will always coast to stop regardless of the selection in parameter P3.2.5 Stop Function.
11.7.4.16 (ID 1041) Run Interlock 1