Danfoss VACON 100 FLOW Series Application Manual page 203

Hide thumbs Also See for VACON 100 FLOW Series:
Table of Contents

Advertisement

VACON® 100 FLOW
Application Guide
Use this parameter to select the digital input signal that starts the timer. The timer starts when this signal is deactivated (falling
edge). The output is deactivated when the time defined in the duration parameter has elapsed.
11.7.4.28 (ID 448) Timer 2
Location in the menu: P3.5.1.28
Use this parameter to select the digital input signal that starts the timer. The timer starts when this signal is deactivated (falling
edge). The output is deactivated when the time defined in the duration parameter has elapsed.
11.7.4.29 (ID 449) Timer 3
Location in the menu: P3.5.1.29
Use this parameter to select the digital input signal that starts the timer. The timer starts when this signal is deactivated (falling
edge). The output is deactivated when the time defined in the duration parameter has elapsed.
11.7.4.30 (ID 1046) PID Setpoint Boost
Location in the menu: P3.5.1.30
Use this parameter to select the digital input signal that activates the boost for the PID setpoint value. The timer starts when this
signal is deactivated (falling edge). The output is deactivated when the time defined in the duration parameter has elapsed.
11.7.4.31 (ID 1047) PID Setpoint Selection
Location in the menu: P3.5.1.31
Use this parameter to set the digital input signal that selects the PID setpoint value to be used.
11.7.4.32 (ID 1049) External PID Start Signal
Location in the menu: P3.5.1.32
Use this parameter to select the digital input signal that starts and stops the external PID controller.
This parameter has no effect if the external PID controller is not enabled in Group 3.14.
11.7.4.33 (ID 1048) External PID Setpoint Selection
Location in the menu: P3.5.1.33
Use this parameter to set the digital input signal that selects the PID setpoint value to be used.
11.7.4.34 (ID 490) Reset Maintenance Counter
Location in the menu: P3.5.1.34
Use this parameter to select the digital input that reset the value of the Maintenance Counter.
11.7.4.35 (ID 530) Flushing Reference Activation
Location in the menu: P3.5.1.36
Use this parameter to select the digital input signal that activates the Flushing function. The flushing frequency reference is bidirec-
tional and a reverse command does not affect the direction of the flushing reference.
If the input is activated, the drive starts.
11.7.4.36 (ID 1596) Fire Mode Activation OPEN
Location in the menu: P3.5.1.38
Use this parameter to select the digital input signal that activates the Fire Mode function. This parameter activates the Fire Mode if it
is enabled with a correct password.
11.7.4.37 (ID 1619) Fire Mode Activation CLOSE
Location in the menu: P3.5.1.39
Danfoss A/S © 2023.08
N O T I C E
N O T I C E
Parameter Descriptions
AB298035655957en-000201 / DPD01083 | 203

Advertisement

Table of Contents
loading

Table of Contents