VACON® 100 FLOW
Application Guide
12.3.146 Fault Code 109, ID 1109 - Input Pressure Supervision
Cause
The supervision signal of the input pressure (P3.13.9.2) is lower than the alarm limit (P3.13.9.7).
Troubleshooting
Check the process.
Check the parameters in menu M3.13.9.
Check the input pressure sensor and connections.
12.3.147 Fault Code 109, ID 1409 - Input Pressure Supervision
Cause
The supervision signal of the input pressure (P3.13.9.2) is lower than the fault limit (P3.13.9.8).
Troubleshooting
Check the process.
Check the parameters in menu M3.13.9.
Check the input pressure sensor and connections.
12.3.148 Fault Code 111, ID 1315 - Temperature Fault 1
Cause
1 or more of the temperature input signals (set in P3.9.6.1) is higher than the alarm limit (P3.9.6.2).
Troubleshooting
Find the cause of the temperature rise.
Check the temperature sensor and connections.
If no sensor is connected, make sure that the temperature input is hardwired.
See the option board manual for more data.
12.3.149 Fault Code 111, ID 1316 - Temperature Fault 1
Cause
1 or more of the temperature input signals (set in P3.9.6.1) is higher than the fault limit (P3.9.6.3).
Troubleshooting
Find the cause of the temperature rise.
Check the temperature sensor and connections.
If no sensor is connected, make sure that the temperature input is hardwired.
See the option board manual for more data.
12.3.150 Fault Code 112, ID 1317 - Temperature Fault 2
Cause
1 or more of the temperature input signals (set in P3.9.6.5) is higher than the fault limit (P3.9.6.6).
Troubleshooting
Find the cause of the temperature rise.
Check the temperature sensor and connections.
If no sensor is connected, make sure that the temperature input is hardwired.
See the option board manual for more data.
12.3.151 Fault Code 112, ID 1318 - Temperature Fault 2
Cause
1 or more of the temperature input signals (set in P3.9.6.5) is higher than the fault limit (P3.9.6.7).
Danfoss A/S © 2023.08
Fault Tracing
AB298035655957en-000201 / DPD01083 | 319