Pid Control Application Wizard - Danfoss VACON 100 FLOW Series Application Manual

Hide thumbs Also See for VACON 100 FLOW Series:
Table of Contents

Advertisement

VACON® 100 FLOW
Application Guide
Index
Parameter
P3.2.5
Stop Function
P3.4.1.2
Acceleration Time
P3.4.1.3
Deceleration Time
If process is set to Compressor, also step 2 is shown. If the selection is anything else, the wizard skips step 2. If
process is set to Other, also steps 11 and 12 are shown.
2.
Set a value for P3.2.11 Restart Delay.
3.
Set a value for P3.1.2.2 Motor Type (so that it agrees with the nameplate of the motor).
If Motor Type is set to Induction Motor, also step 8 is shown. If the selection is PM Motor, the value of parameter
P3.1.1.5 Motor Cos Phi is set to 1.00, and the wizard skips step 8.
4.
Set a value for P3.1.1.1 Motor Nominal Voltage (so that it agrees with the nameplate of the motor).
5.
Set a value for P3.1.1.2 Motor Nominal Frequency (so that it agrees with the nameplate of the motor).
6.
Set a value for P3.1.1.3 Motor Nominal Speed (so that it agrees with the nameplate of the motor).
7.
Set a value for P3.1.1.4 Motor Nominal Current (so that it agrees with the nameplate of the motor).
8.
Set a value for P3.1.1.5 Motor Cos Phi (so that it agrees with the nameplate of the motor).
9.
Set a value for P3.3.1.1 Minimum Frequency Reference.
10.
Set a value for P3.3.1.2 Maximum Frequency Reference.
11.
Set a value for P3.4.1.2 Acceleration Time 1.
12.
Set a value for P3.4.1.3 Deceleration Time 1.
The wizard goes to steps specified by the application.
13.
Select the control place (where to give the start and stop commands, and the frequency reference of the drive).
The HVAC application wizard is completed.

4.1.3 PID Control Application Wizard

The application wizard helps to set the basic parameters that are related to the application.
To start the PID Control application wizard, set the value PID Control to parameter P1.2 Application (ID 212) in the keypad.
If the application wizard is started from the Start-up wizard, the wizard goes directly to step 11.
See the range of values of the parameters in
Brakes
Setup,
6.13 Group 3.13: PID
Procedure
1.
Set a value for P3.1.2.2 Motor Type (so that it agrees with the nameplate of the motor).
If Motor Type is set to Induction Motor, also step 6 is shown. If the selection is PM Motor, the value of parameter
P3.1.1.5 Motor Cos Phi is set to 1.00, and the wizard skips step 6.
2.
Set a value for P3.1.1.1 Motor Nominal Voltage (so that it agrees with the nameplate of the motor).
3.
Set a value for P3.1.1.2 Motor Nominal Frequency (so that it agrees with the nameplate of the motor).
4.
Set a value for P3.1.1.3 Motor Nominal Speed (so that it agrees with the nameplate of the motor).
5.
Set a value for P3.1.1.4 Motor Nominal Current (so that it agrees with the nameplate of the motor).
6.
Set a value for P3.1.1.5 Motor Cos Phi (so that it agrees with the nameplate of the motor).
7.
Set a value for P3.3.1.1 Minimum Frequency Reference.
8.
Set a value for P3.3.1.2 Maximum Frequency Reference.
9.
Set a value for P3.4.1.2 Acceleration Time 1.
10.
Set a value for P3.4.1.3 Deceleration Time 1.
11.
Select a control place (where to give the start and stop commands, and the frequency reference of the drive).
Danfoss A/S © 2023.08
6.1 Group 3.1: Motor
Controller.
Process type
Pump
Fan
Ramping
Coasting
5.0 s
30.0 s
5.0 s
30.0 s
Settings,
6.3 Group 3.3:
References,
Compressor
Ramping
3.0 s
3.0 s
6.4 Group 3.4: Ramps and
AB298035655957en-000201 / DPD01083 | 69