VACON® 100 FLOW
Application Guide

4 Wizards

4.1 Application Wizards

4.1.1 Standard Application Wizard

The application wizard helps to set the basic parameters that are related to the application.
To start the Standard application wizard, set the value Standard to parameter P1.2 Application (ID 212) in the keypad.
If the application wizard is started from the Start-up wizard, the wizard goes directly to step 11.
See the range of values of the parameters in
Brakes
Setup.
Procedure
1.
Set a value for P3.1.2.2 Motor Type (so that it agrees with the nameplate of the motor).
If Motor Type is set to Induction Motor, also step 6 is shown. If the selection is PM Motor, the value of parameter
P3.1.1.5 Motor Cos Phi is set to 1.00, and the wizard skips step 6.
2.
Set a value for P3.1.1.1 Motor Nominal Voltage (so that it agrees with the nameplate of the motor).
3.
Set a value for P3.1.1.2 Motor Nominal Frequency (so that it agrees with the nameplate of the motor).
4.
Set a value for P3.1.1.3 Motor Nominal Speed (so that it agrees with the nameplate of the motor).
5.
Set a value for P3.1.1.4 Motor Nominal Current (so that it agrees with the nameplate of the motor).
6.
Set a value for P3.1.1.5 Motor Cos Phi (so that it agrees with the nameplate of the motor).
7.
Set a value for P3.3.1.1 Minimum Frequency Reference.
8.
Set a value for P3.3.1.2 Maximum Frequency Reference.
9.
Set a value for P3.4.1.2 Acceleration Time 1.
10.
Set a value for P3.4.1.3 Deceleration Time 1.
11.
Select the a control place (where to give the start and stop commands, and the frequency reference of the drive).
The Standard application wizard is completed.

4.1.2 HVAC Application Wizard

The application wizard helps to set the basic parameters that are related to the application.
To start the HVAC application wizard, set the value Standard to parameter P1.2 Application (ID 212) in the keypad.
See the range of values of the parameters in
ces,
6.4 Group 3.4: Ramps and Brakes
Procedure
1.
Select the type or process (or application) to control.
-
Compressor
-
Fan
-
Pump
-
Other
Some parameters have preset values specified by the selection. See the parameters and their values in the following table.
Table 11: Preset Values of Parameters
Index
Parameter
P3.1.4.1
U/f Ratio
P3.2.4
Start Function
68 | Danfoss A/S © 2023.08
6.1 Group 3.1: Motor
Settings,
6.2 Group 3.2: Start/Stop
Setup.
Process type
Pump
Linear
Ramping
6.3 Group 3.3:
References,
Setup,
6.1 Group 3.1: Motor
Settings,
Fan
Squared
Flying start
AB298035655957en-000201 / DPD01083
Wizards
6.4 Group 3.4: Ramps and
6.3 Group 3.3: Referen-
Compressor
Linear
Ramping