This fault is only used with enclosure sizes MR11 and MR12.
12.3.49 Fault Code 18, ID 171 - Unbalance
Cause
The DC voltage is unbalanced between power units.
Troubleshooting
Check the DC link cables between the power units.
Check the motor cables and connections.
Check the output filters (dU/dt filter, sine filter).
Reset the fault and restart the drive.
If the fault occurs again, ask for instructions from your nearest service center or distributor. Report carefully all the used soft-
ware, application, and options.
This fault is only used with enclosure sizes MR11 and MR12.
12.3.50 Fault Code 18, ID 173 - Unbalance (Alarm)
Cause
The current is unbalanced between power units.
Troubleshooting
Check the installation and the motor cables.
Redo the IGBT ID run.
The event response can be set to No Action.
This fault is only used with enclosure sizes MR11 and MR12.
12.3.51 Fault Code 19, ID 180 - Power Overload (Short-time Supervision)
Cause
The power of the drive is too high.
Troubleshooting
Decrease the load.
Examine the dimensions of drive. Examine if it is too small for the load.
12.3.52 Fault Code 19, ID 181 - Power Overload (Long-time Supervision)
Cause
The power of the drive is too high.
Troubleshooting
Decrease the load.
Examine the dimensions of drive. Examine if it is too small for the load.
12.3.53 Fault Code 25, ID 240 - Motor Control Fault
Cause
This fault is available only if you use a customer-specific application. A malfunction in the start angle identification.
The rotor moves during identification.
The new angle does not agree with the old value.
Danfoss A/S © 2023.08
N O T I C E
N O T I C E
N O T I C E
Fault Tracing
AB298035655957en-000201 / DPD01083 | 305