This fault is only used with enclosure sizes MR11 and MR12.
12.3.49 Fault Code 18, ID 171 - Unbalance
Cause
•
The DC voltage is unbalanced between power units.
Troubleshooting
•
Check the DC link cables between the power units.
•
Check the motor cables and connections.
•
Check the output filters (dU/dt filter, sine filter).
•
Reset the fault and restart the drive.
•
If the fault occurs again, ask for instructions from your nearest service center or distributor. Report carefully all the used soft-
ware, application, and options.
This fault is only used with enclosure sizes MR11 and MR12.
12.3.50 Fault Code 18, ID 173 - Unbalance (Alarm)
Cause
•
The current is unbalanced between power units.
Troubleshooting
•
Check the installation and the motor cables.
•
Redo the IGBT ID run.
•
The event response can be set to No Action.
This fault is only used with enclosure sizes MR11 and MR12.
12.3.51 Fault Code 19, ID 180 - Power Overload (Short-time Supervision)
Cause
•
The power of the drive is too high.
Troubleshooting
•
Decrease the load.
•
Examine the dimensions of drive. Examine if it is too small for the load.
12.3.52 Fault Code 19, ID 181 - Power Overload (Long-time Supervision)
Cause
•
The power of the drive is too high.
Troubleshooting
•
Decrease the load.
•
Examine the dimensions of drive. Examine if it is too small for the load.
12.3.53 Fault Code 25, ID 240 - Motor Control Fault
Cause
This fault is available only if you use a customer-specific application. A malfunction in the start angle identification.
•
The rotor moves during identification.
•
The new angle does not agree with the old value.