VACON® 100 FLOW
Application Guide
Procedure
1.
Set a value for parameter P3.17.2 Fire Mode Frequency Source.
If other value than Fire mode frequency is selected, the wizard goes directly to step 3.
2.
Set a value for parameter P3.17.3 Fire Mode Frequency.
3.
Activate the signal when the contact opens or when it closes.
4.
Set a value for parameters P3.17.4 Fire Mode Activation on OPEN/P3.17.5 Fire Mode Activation on CLOSE.
See also chapter
11.7.1.1 General Information on the
5.
Set a value for parameter P3.17.6 Fire Mode Reverse.
6.
Set a value for P3.17.1 Fire Mode Password.
74 | Danfoss A/S © 2023.08
Programming.
Wizards
AB298035655957en-000201 / DPD01083