Application Guide
Troubleshooting
Check the external safety switch. Check the input connection and cable of the safety switch.
Reset the drive and restart.
If the fault occurs again, ask for instructions from your nearest distributor.
12.3.68 Fault Code 30, ID 521 - Safety diagnostics
Cause
A malfunction in the ATEX thermistor diagnostic. There is no connection in the ATEX thermistor input.
Troubleshooting
Reset the drive and restart.
If the fault occurs again, change the option board.
12.3.69 Fault Code 30, ID 522 - Safety diagnostics
Cause
A short circuit in the connection of the ATEX thermistor input.
Troubleshooting
Check the ATEX thermistor input connection.
Check the external ATEX connection.
Check the external ATEX thermistor.
12.3.70 Fault Code 30, ID 530 - Safe Torque Off
Cause
An emergency stop was connected or some other STO operation was activated.
Troubleshooting
When the STO function is activated, the drive is in safe state.
12.3.71 Fault Code 32, ID 311 - Fan Cooling
Cause
The fan speed does not agree to the speed reference accurately, but the drive operates correctly.
This fault shows only in the MR7 and in enclosure sizes bigger than MR7.
Troubleshooting
Reset the fault and restart the drive.
Clean or replace the fan.
12.3.72 Fault Code 32, ID 312 - Fan Cooling
Cause
The fan life time (that is, 50 000 h) is complete.
Troubleshooting
Replace the fan and reset the life time counter of the fan.
12.3.73 Fault Code 33, ID 320 - Fire Mode Enabled
Cause
The fire mode of the drive is enabled. The protections of the drive are disabled or autoreset.
Troubleshooting
Check the parameter settings and the signals.
This alarm is reset automatically when fire mode is disabled.
308 | Danfoss A/S © 2023.08
Fault Tracing
AB298035655957en-000201 / DPD01083