C
Reference
11.15.2 Setpoints
11.15.2.1 (ID 167) Keypad Setpoint 1
Location in the menu: P3.13.2.1
Use this parameter to set the setpoint value of the PID controller when the setpoint source is 'Keypad SP'. The value of this parame-
ter is given in the selected process unit.
11.15.2.2 (ID 168) Keypad Setpoint 2
Location in the menu: P3.13.2.2
Use this parameter to set the setpoint value of the PID controller when the setpoint source is 'Keypad SP'. The value of this parame-
ter is given in the selected process unit.
11.15.2.3 (ID 1068) Setpoint Ramp Time
Location in the menu: P3.13.2.3
Use this parameter to set the rising and falling ramp times for the setpoint changes. Ramp time is the time that is necessary for the
setpoint value to change from minimum to maximum. If the value of this parameter is set to 0, no ramps are used.
11.15.2.4 (ID 1046) PID Setpoint Boost Activation
Location in the menu: P3.13.2.4
Use this parameter to select the digital input signal that activates the boost for the PID setpoint value.
11.15.2.5 (ID 1047) PID Setpoint Selection
Location in the menu: P3.13.2.5
Use this parameter to set the digital input signal that selects the PID setpoint value to be used.
11.15.2.6 (ID 332) Setpoint Source 1 Selection
Location in the menu: P3.13.2.6
Use this parameter to select the source of the PID setpoint signal. The AIs and the ProcessDataIn are handled as percentages (0.00–
100.00%) and scaled according to the setpoint minimum and maximum.
The ProcessDataIn signals use 2 decimals.
If temperature inputs are selected, the values of parameters P3.13.1.5 Process Unit Min and P3.13.1.6 Process Unit Max must be set
to correspond to the scale of the temperature measurement board: ProcessUnitMin = -50 °C and ProcessUnitMax = 200 °C.
11.15.2.7 (ID 1069) Setpoint 1 Minimum
Location in the menu: P3.13.2.7
Use this parameter to set the minimum value of the setpoint signal.
11.15.2.8 (ID 1070) Setpoint 1 Maximum
Location in the menu: P3.13.2.8
Use this parameter to set the maximum value of the setpoint signal.
11.15.2.9 (ID 1071) Setpoint 1 Boost
Location in the menu: P3.13.2.9
Use this parameter to set the multiplier for the setpoint boost function. When the setpoint boost command is given, the setpoint
value is multiplied by the factor that is set with this parameter.
238 | Danfoss A/S © 2023.08
D
Actual value
E
Output locked
AB298035655957en-000201 / DPD01083
Parameter Descriptions