2.4.2 Editing the Numerical Values

This topic gives instructions on how to edit the numerical values on the text display.
Procedure
1.
Find the parameter with the arrow buttons.
2.
Go to the Edit mode.
3.
Move from digit to digit with the arrow buttons Left and Right. Change the digits with the arrow buttons Up and Down.
4.
Accept the change with the [OK] button. To ignore the change, use the [BACK/RESET] button.
2.4.3 Resetting a Fault
To reset a fault, use the [BACK/RESET] button or the parameter Reset Faults. See

2.4.4 [FUNCT] Button

The [FUNCT] button can be used for 4 functions.
To have access to the Control page.
To change easily between the Local and Remote control places.
To change the rotation direction.
To edit quickly a parameter value.
2.4.4.1 Different Control Places
The selection of the control place determines from where the AC drive takes the start and stop commands. All the control places
have a parameter for the selection of the frequency reference source. The Local control place is always Keypad. The Remote control
place is I/O or Fieldbus. The status bar of the display shows the current control place.
It is possible to use I/O A, I/O B, and Fieldbus as Remote control places. I/O A and Fieldbus have the lowest priority. Select them with
P3.2.1 (Remote Control Place). I/O B can bypass the Remote control places I/O A and Fieldbus with a digital input. Select the digital
input with parameter P3.5.1.7 (I/O B Control Force).
Keypad is always used as a control place when the control place is Local. Local control has higher priority than Remote control. For
example, if parameter P3.5.1.7 bypasses the control place with a digital input, and Local is selected in Remote control, Keypad be-
comes the control place. Use the [FUNCT] button or P3.2.2 Local/Remote to change between the Local and Remote control.

2.4.4.2 Changing the Control Place

This topic gives instructions on how to change the control place on the control panel.
Procedure
1.
Anywhere in the menu structure, push the [FUNCT] button.
2.
To select Local/Remote, use the arrow buttons Up and Down. Push the [OK] button.
Danfoss A/S © 2023.08
7.1.2 Reset
Faults.
AB298035655957en-000201 / DPD01083 | 25