VACON® 100 FLOW
Application Guide
11.13 Application Settings
11.13.1 (ID 1806) Password
Location in the menu: P3.11.1
Use this parameter to set the administrator password.
11.13.2 (ID 1197) C/F Selection
Location in the menu: P3.11.2
Use this parameter to set the temperature measuring unit. The system shows all the temperature-related parameters and monitor-
ing values in the set unit.
11.13.3 (ID 1198) kW/HP Selection
Location in the menu: P3.11.3
Use this parameter to set the power measuring unit. The system shows all the power-related parameters and monitoring values in
the set unit.
11.13.4 (ID 1196) Multimonitor View
Location in the menu: P3.11.4
Use this parameter to set the division of the display of the control panel into sections in the multimonitor view.
11.13.5 (ID 1195) [FUNCT] Button Configuration
Location in the menu: P3.11.5
Use this parameter to set the values of the [FUNCT] button. The values set with this parameter are available when pushing the
[FUNCT] button on the keypad.
11.13.6 (ID 1807) Set Parameter Lock
Location in the menu: P3.11.6
Use this parameter to set a password for edit-locking all parameters. Parameters are locked if value is set greater than zero. To disa-
ble the lock, open the lock with a correct key, and set the lock-password back to zero.
NOTE! After setting this parameter to larger than zero (0), the lock is immediately active. Setting a lock also locks and hide this pa-
rameter itself. Control place cannot be changed over to Local, when the lock is in place.
11.13.7 (ID 1808) Parameter Lock Key
Location in the menu: P3.11.7
Use this parameter to enter a password for opening the parameter edit-lock. The lock is opened if the values of the Key- and Lock-
passwords are equal.
11.14 Timer Functions
11.14.1 Introduction to Timer Functions
The timer functions make it possible for the internal RTC (real-time clock) to control functions. All the functions that can be control-
led with a digital input, can also be controlled with the RTC, with time channels 1–3. It is not necessary to have an external PLC to
control a digital input. It is possible program the closed and opened intervals of the input internally.
To get the best results of the timer functions, install a battery, and make the settings of the real-time clock carefully in the Start-up
wizard. The battery is available as an option.
It is not recommended to use the timer functions without an auxiliary battery. The time and date settings of the drive are reset at
each power down, if there is no battery for the RTC.
232 | Danfoss A/S © 2023.08
N O T I C E
Parameter Descriptions
AB298035655957en-000201 / DPD01083