VACON® 100 FLOW
Application Guide
In the following figure, Time Channel 1 is used as the control signal for the start command instead of a digital input.
Interval 1
Days = Monday to Friday
ON = 07:00:00 hrs OFF = 17:00:00 hrs
Interval 2
Days = Saturday and Sunday
ON = 09:00:00 hrs OFF = 13:00:00 hrs
Digital input 1
on Slot A
Illustration 75: Time Channel 1 as the Control Signal for the Start Command
11.14.3 Editing an Interval
Procedure
1.
Activate the interval to edit.
2.
Go into parameter Days (ID 1466).
STOP
ON Time
OFF Time
Days
3.
Go into the Edit mode.
4.
Select the necessary weekdays in the checkbox selection.
STOP
Days
ID:
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
11.14.4 (ID 1464) ON Time
Location in the menu: P3.12.1.1
Use this parameter to set the time of day when the output of the interval function is activated.
11.14.5 (ID 1465) OFF Time
Location in the menu: P3.12.1.2
Use this parameter to set the time of day when the output of the interval function is deactivated.
Danfoss A/S © 2023.08
Timer 1
Duration = 1800 s
READY
I/O
Interval 1
ID:1466
M3.12.1.3
07:00:00
17:00:00
0
READY
I/O
M3.12.1.3.1
P
Ctrl Signal 1A
Time channel 1
AB298035655957en-000201 / DPD01083 | 235
Parameter Descriptions
Start/Stop