Danfoss VACON 100 FLOW Series Application Manual page 106

Hide thumbs Also See for VACON 100 FLOW Series:
Table of Contents

Advertisement

VACON® 100 FLOW
Application Guide
Index
Parameter
P3.9.1.14
Response to Safe Torque Off
(STO) Fault
P3.9.1.17
Fieldbus Communication
Fault Force Delay
P3.9.1.18
Fieldbus Communication
Fault Clear Delay
P3.9.1.19
Unbalance Current Alarm
Table 58: Motor Thermal Protection Settings
Index
Parameter
P3.9.2.1
Motor Thermal Protection
P3.9.2.2
Ambient Temperature
P3.9.2.3
Zero Speed Cooling Factor
P3.9.2.4
Motor Thermal Time Constant
P3.9.2.5
Motor Thermal Loadability
Table 59: Motor Stall Protection Settings
Index
Parameter
P3.9.3.1
Motor Stall Fault
P3.9.3.2
Stall Current
P3.9.3.3
Stall Time Limit
P3.9.3.4
Stall Frequency Limit
Table 60: Motor Underload Protection Settings
Index
Parameter
P3.9.4.1
Underload Fault
106 | Danfoss A/S © 2023.08
Min
Max
Unit
0
2
0.00
320.00
s
0.00
320.00
s
0
1
Min
Max
0
3
-20.0
100.0
5.0
150.0
1
200
10
150
Min
Max
Unit
Default
0
3
0
0.00
Is
A
Varies
1.00
120.00
s
15.00
1.00
P3.3.1.2
Hz
25.00
Min
Max
0
3
Default
ID
Description
2
775
0 = No action
1 = Alarm
2 = Fault (Stop by coasting)
0.00
751
0.00
752
1
753
Unit
Default
ID
Description
2
704
0 = No action
1 = Alarm
2 = Fault (Stop by stop mode)
3 = Fault (Stop by coasting)
°C
40.0
705
%
Varies
706
min
15
707
%
100
708
ID
Description
709
0 = No action
1 = Alarm
2 = Fault (Stop according to stop mode)
3 = Fault (Stop by coasting)
710
711
712
Unit
Default
ID
Description
0
713
0 = No action
1 = Alarm
2 = Fault (Stop according to stop
mode)
AB298035655957en-000201 / DPD01083