Danfoss VACON 100 FLOW Series Application Manual page 66

Hide thumbs Also See for VACON 100 FLOW Series:
Table of Contents

Advertisement

VACON® 100 FLOW
Application Guide
Table 10: M1.34 Multi-pump (Multidrive)
Index
Parameter
1.35.1
PID Gain
1.35.2
PID Integration Time
1.35.3
PID Derivation Time
1.35.4
Process Unit Selection
1.35.5
Process Unit Min
1.35.6
Process Unit Max
1.35.7
Feedback 1 Source Selection
1.35.8
Setpoint 1 Source Selection
1.35.9
Keypad Setpoint 1
1.35.10
SP1 Sleep Frequency Limit
1.35.11
SP1 Sleep Delay
1.35.12
SP1 Wake Up Level
1.35.13
Multi-pump Mode
1.35.14
Number of Pumps
1.35.15
Pump ID Number
1.35.16
Start and Feedback Signals
1.35.17
Pump Interlocking
1.35.18
Autochange
1.35.19
Autochanged Pump
1.35.20
Autochange Interval
1.35.21
Autochange Days
1.35.22
Autochange Time of Day
1.35.23
Autochange: Frequency Limit
1.35.24
Autochange: Pump Limit
66 | Danfoss A/S © 2023.08
Min
Max
0.00
100.00
0.00
600.00
0.00
100.00
1
44
Varies
Varies
Varies
Varies
0
30
0
32
Varies
Varies
0.0
320.0
0
3000
Varies
Varies
0
2
1
8
1
8
0
2
0
1
0
2
0
1
0.0
3000.0
0
127
0.00
P3.3.1.2
1
6
Unit
Default
ID
%
100.00
118
s
1.00
119
s
0.00
132
1
1036
Varies
1033
Varies
1034
2
334
1
332
Varies
0
167
Hz
0.0
1016
s
0
1017
Varies
Varies
1018
0
1785
1
1001
1
1500
1
1782
1
1032
1
1027
1
1028
h
48.0
1029
1786
Time
1787
Hz
25:00
1031
1030
AB298035655957en-000201 / DPD01083
Applications
Description
See P3.13.1.4
See P3.13.3.3
See P3.13.2.6
0 = Not used
0 = Not used
0= Single drive
1= Multifollower
2= Multimaster
0 = Not connected
1 = Only Start Signal Con-
nected
2 = Both Signals Connec-
ted
0 = Disabled
1 = Enabled
0 = Disabled
1 = Enabled (interval)
2 = Enabled (weekdays)
0 = Auxiliary Pump
1 = All Pumps