12.3.117 Fault Code 65, ID 1065 - PC Communication Fault
Cause
•
The data connection between the PC and the drive is defective.
Troubleshooting
•
Check the installation, cable, and terminals between the PC and the drive.
12.3.118 Fault Code 66, ID 1366 - Thermistor Input 1 Fault
Cause
•
The motor temperature increased.
Troubleshooting
•
Check the motor cooling and the load.
•
Check the thermistor connection.
•
If the thermistor input is not used, you have to short-circuit it.
•
Ask for instructions from your nearest distributor.
12.3.119 Fault Code 66, ID 1466 - Thermistor Input 2 Fault
Cause
•
The motor temperature increased.
Troubleshooting
•
Check the motor cooling and the load.
•
Check the thermistor connection.
•
If the thermistor input is not used, you have to short-circuit it.
•
Ask for instructions from your nearest distributor.
12.3.120 Fault Code 66, ID 1566 - Thermistor Input 3 Fault
Cause
•
The motor temperature increased.
Troubleshooting
•
Check the motor cooling and the load.
•
Check the thermistor connection.
•
If the thermistor input is not used, you have to short-circuit it.
•
Ask for instructions from your nearest distributor.
12.3.121 Fault Code 68, ID 1301 - Maintenance Counter 1 Alarm
Cause
•
The value of the maintenance counter is higher than the alarm limit.
Troubleshooting
•
Do the necessary maintenance.
•
Reset the counter. See parameter B3.16.4 or P3.5.1.40.
12.3.122 Fault Code 68, ID 1302 - Maintenance Counter 1 Fault
Cause
•
The value of the maintenance counter is higher than the fault limit.
Troubleshooting
•
Do the necessary maintenance.
•
Reset the counter. See parameter B3.16.4 or P3.5.1.40.