VACON® 100 FLOW
Application Guide
Troubleshooting
Set the option board parameters again.
12.3.96 Fault Code 45, ID 445 - Device Added (Different Type)
Cause
A new option board, that you have not used before in the same slot, was put in slot E. No parameter settings are saved.
Troubleshooting
Set the option board parameters again.
12.3.97 Fault Code 46, ID 662 - Real Time Clock
Cause
The voltage of the RTC battery is low.
Troubleshooting
Replace the battery.
12.3.98 Fault Code 47, ID 663 - Software Updated
Cause
The software of the drive was updated, the full software package or an application.
Troubleshooting
No steps are necessary.
12.3.99 Fault Code 50, ID 1050 - AI Low Fault
Cause
1 or more of the available analog input signals is below 50% of the minimum signal range.
A control cable is defective or loose.
A malfunction in a signal source.
Troubleshooting
Replace the defective parts.
Check the analog input circuit.
Make sure that parameter AI1 Signal Range is set correctly.
12.3.100 Fault Code 51, ID 1051 - Device External Fault
Cause
The digital input signal that is set with parameter P3.5.1.11 or P3.5.1.12 was activated.
Troubleshooting
This is a user-defined fault.
Check the digital inputs and schematics.
12.3.101 Fault Code 52, ID 1052 - Keypad Communication Fault
Cause
The connection between the control panel and the drive is defective.
Troubleshooting
Check the control panel connection and the control panel cable if you have it.
12.3.102 Fault Code 52, ID 1352 - Keypad Communication Fault
Cause
The connection between the control panel and the drive is defective.
312 | Danfoss A/S © 2023.08
Fault Tracing
AB298035655957en-000201 / DPD01083