12.3.110 Fault Code 54, ID 1754 - Slot E fault
Cause
A defective option board or slot.
Troubleshooting
Check the board and the slot.
Ask for instructions from your nearest distributor.
12.3.111 Fault Code 57, ID 1057 - Identification
Cause
There was a failure in the identification run.
Troubleshooting
Make sure that the motor is connected to the drive.
Make sure that there is no load on the motor shaft.
Make sure that the start command is not removed before the identification run is complete.
12.3.112 Fault Code 57, ID 1157 - Identification
Cause
During the identification run, drive was not able to reach required frequency reference.
Troubleshooting
Make sure that minimum and maximum frequency references are set correctly. Too low maximum frequency can prevent drive
from reaching required frequency.
12.3.113 Fault Code 57, ID 1257 - Identification
Cause
During the identification run, drive was not able to reach required frequency reference.
Troubleshooting
Make sure that acceleration time is set correctly. Too long acceleration time can prevent drive from reaching required frequency
in 40 seconds.
12.3.114 Fault Code 57, ID 1357 - Identification
Cause
During the identification run, drive was not able to reach required frequency reference.
Troubleshooting
Make sure that current, torque, and power limits of the drive are set correctly. Too low limit settings can prevent drive from
reaching required frequency.
12.3.115 Fault Code 63, ID 1063 - Quick Stop Fault
Cause
The quick stop function is activated.
Troubleshooting
Find the cause for the quick stop activation. After you find it, correct it. Reset the fault and restart the drive.
See parameter P3.5.1.26 and the quick stop parameters.
12.3.116 Fault Code 63, ID 1363 - Quick Stop Alarm
Cause
The quick stop function is activated.
Troubleshooting
Find the cause for the quick stop activation. After you find it, correct it. Reset the fault and restart the drive.
See parameter P3.5.1.26 and the quick stop parameters.