VACON® 100 FLOW
Application Guide
PT
B
Illustration 85: The Location of the Pressure Sensor
A
Mains
B
Inlet
Input Pressure
Supervision
Alarm Level
Supervision
Fault Level
PID Setpoint
PID Setpoint
Input Pressure Alarm
(Digital output signal)
Motor Running
Illustration 86: The Input Pressure Supervision Function
11.15.9.1 (ID 1685) Enable Supervision
Location in the menu: P3.13.9.1
Use this parameter to enable the Input Pressure Supervision function. Use this function to make sure that there is enough fluid in
the inlet of the pump.
11.15.9.2 (ID 1686) Supervision Signal
Location in the menu: P3.13.9.2
Use this parameter to select the source of the input pressure signal.
248 | Danfoss A/S © 2023.08
A
C
Input Pressure Monitor
Supervision
Fault Delay
C
Outlet
Supervision
Fault Delay
PID Setpoint
Reduction
Parameter Descriptions
Yes
No
AB298035655957en-000201 / DPD01083