Danfoss VACON 100 FLOW Series Application Manual page 210

Hide thumbs Also See for VACON 100 FLOW Series:
Table of Contents

Advertisement

VACON® 100 FLOW
Application Guide
Selection
Selection name
number
0
Not used
1
Ready
2
Run
3
General fault
4
General fault inverted
5
General alarm
6
Reversed
7
At speed
8
Thermistor fault
9
Motor regulator activated
10
Start signal active
11
Keypad control active
12
I/O control B active
13
Limit supervision 1
14
Limit supervision 2
15
Fire mode active
16
Flushing active
17
Preset Frequency active
18
Quick Stop active
19
PID in Sleep mode
20
PID Soft Fill activated
21
PID feedback supervision
22
ExtPID feedback supervision
23
Input pressure alarm
24
Frost protection alarm
25
Time channel 1
26
Time channel 2
27
Time channel 3
28
Fieldbus Control Word bit 13
29
Fieldbus Control Word bit 14
210 | Danfoss A/S © 2023.08
Description
The output is not used.
The AC drive is ready to operate.
The AC drive operates (the motor runs).
A fault trip occurred.
A fault trip did not occur.
An alarm occurred.
The reverse command is given.
The output frequency has become the same as the set frequency reference.
A thermistor fault occurred.
One of the limit regulators (for example current limit or torque limit) is activated.
The start command of the drive is active.
The selection is keypad control (the active control place is keypad).
The selection is I/O control place B (the active control place is I/O B).
The limit supervision activates if the signal value goes below or above the set su-
pervision limit (P3.8.3 or P3.8.7).
The limit supervision activates if the signal value goes below or above the set su-
pervision limit (P3.8.3 or P3.8.7).
The Fire mode function is active.
The Flushing function is active.
The selection of preset frequency was made with digital input signals.
The Quick stop function is activated.
The PID controller is in the sleep mode.
The Soft fill function of the PID controller is activated.
The feedback value of the PID controller is not in the supervision limits.
The External PID controller feedback value is not in the supervision limits.
The input pressure of the pump is below the value that was set with parameter
P3.13.9.7.
The measured temperature of the pump is below the level that was set with pa-
rameter P3.13.10.5.
The status of Time channel 1.
The status of Time channel 2.
The status of Time channel 3.
The digital (relay) output control from the Fieldbus control word bit 13.
The digital (relay) output control from the Fieldbus control word bit 14.
Parameter Descriptions
AB298035655957en-000201 / DPD01083