Danfoss VACON 100 FLOW Series Application Manual page 128

Hide thumbs Also See for VACON 100 FLOW Series:
Table of Contents

Advertisement

VACON® 100 FLOW
Application Guide
Index
Parameter
P3.21.1.2
Cleaning Activation
P3.21.1.3
Cleaning Current Limit
P3.21.1.4
Cleaning CurrentDelay
P3.21.1.5
Cleaning Weekdays
P3.21.1.6
Cleaning Time of Day
P3.21.1.7
Cleaning Cycles
P3.21.1.8
Clean Forward Frequency
P3.21.1.9
Clean Forward Time
P3.21.1.10
Clean Reverse Frequency
P3.21.1.11
Clean Reverse Time
P3.21.1.12
Cleaning Acceleration Time
P3.21.1.13
Cleaning Deceleration Time
Table 100: Jockey Pump Parameters
Index
Parameter
P3.21.2.1
Jockey Function
P3.21.2.2
Jockey Start Level
P3.21.2.3
Jockey Stop Level
Table 101: Priming Pump Parameters
Index
Parameter
P3.21.3.1
Priming Function
P3.21.3.2
Priming Time
128 | Danfoss A/S © 2023.08
Min
Max
Unit
0.0
200.0
%
0.0
300.0
s
0
127
00:00:00
23:59:59
1
100
0.00
50.00
Hz
0.00
320.00
s
0.00
50.00
Hz
0.00
320.00
s
0.1
300.0
s
0.1
300.0
s
Min
Max
Unit
0
2
Varies
Varies
Varies
Varies
Varies
Varies
Min
Max
0
1
0.0
320.00
Default
ID
DigINSlot0.1
1715
120.0
1712
60.0
1713
0
1723
00:00:00
1700
5
1716
45.00
1717
2.00
1718
45.00
1719
0.00
1720
0.1
1721
0.1
1722
Default
ID
0
1674
0.00
1675
0.00
1676
Unit
Default
ID
0
1677
3.0
1678
AB298035655957en-000201 / DPD01083
Parameters Menu
Description
3 = Enabled (weekdays)
B0 = Sunday
B1 = Monday
B2 = Tuesday
B3 = Wednesday
B4 = Thursday
B5 = Friday
B6 = Saturday
Description
0 = Not used
1 = PID sleep
2 = PID sleep (level)
Description
0 = Disabled
1 = Enabled

Advertisement

Table of Contents
loading