VACON® 100 FLOW
Application Guide
Troubleshooting
•
Find the cause of the temperature rise.
•
Check the temperature sensor and connections.
•
If no sensor is connected, make sure that the temperature input is hardwired.
•
See the option board manual for more data.
12.3.152 Fault Code 113, ID 1113 - Pump Running Time
Cause
•
In the Multi-pump system, 1 or more of the pump run-time counters is above a user-specified alarm limit.
Troubleshooting
•
Do the necessary maintenance actions, reset the run-time counter, and reset the alarm. See Pump running time counters.
12.3.153 Fault Code 113, ID 1313 - Pump Running Time
Cause
•
In the Multi-pump system, 1 or more of the pump run-time counters is above a user-specified alarm limit.
Troubleshooting
•
Do the necessary maintenance actions, reset the run-time counter, and reset the alarm. See Pump running time counters.
12.3.154 Fault Code 117, ID 1117 - Flow Switch
Cause
•
The feedback signal from the flow switch was inactive longer than the specified flow switch fault delay time.
Troubleshooting
•
Do a check of the process.
•
Do a check of the parameter settings.
12.3.155 Fault Code 118, ID 1118 - AHF Over Temp
Cause
•
The advanced harmonic filter function has caused an overtemperature fault through a digital input.
Troubleshooting
•
Check the advanced harmonic filter function.
12.3.156 Fault Code 119, ID 1119 - Auto Cleaning
Cause
•
The motor did not reach the expected speed reference during the auto cleaning sequence.
Troubleshooting
•
Check the process.
•
Check the auto cleaning parameter settings.
12.3.157 Fault Code 300, ID 700 - Unsupported
Cause
•
The application is not compatible (it is unsupported).
Troubleshooting
•
Replace the application.
12.3.158 Fault Code 300, ID 701 - Unsupported
Cause
•
The option board or the slot is not compatible (it is unsupported).