Examine the heatsink for dust.
Make sure that the switching frequency is not too high in relation to the ambient temperature and the motor load.
Check the cooling fan.
Make an identification run.
12.3.89 Fault Code 44, ID 431 - Device Changed (Different Type)
Cause
There is a new power unit of a different type. Parameters are not available in the settings.
Troubleshooting
Reset the fault. The drive reboots after you reset the fault.
Set the power unit parameters again.
12.3.90 Fault Code 44, ID 433 - Device Changed (Different Type)
Cause
The option board in slot C was replaced by a new one that you have not used before in the same slot. No parameter settings are
saved.
Troubleshooting
Reset the fault. Set the option board parameters again.
12.3.91 Fault Code 44, ID 434 - Device Changed (Different Type)
Cause
The option board in slot D was replaced by a new one that you have not used before in the same slot. No parameter settings are
saved.
Troubleshooting
Reset the fault. Set the option board parameters again.
12.3.92 Fault Code 44, ID 435 - Device Changed (Different Type)
Cause
The option board in slot E was replaced by a new one that you have not used before in the same slot. No parameter settings are
saved.
Troubleshooting
Reset the fault. Set the option board parameters again.
12.3.93 Fault Code 45, ID 441 - Device Added (Different Type)
Cause
There is a new power unit of a different type. Parameters are not available in the settings.
Troubleshooting
Reset the fault. The drive reboots after you reset the fault.
Set the power unit parameters again.
12.3.94 Fault Code 45, ID 443 - Device Added (Different Type)
Cause
A new option board, that you have not used before in the same slot, was put in slot C. No parameter settings are saved.
Troubleshooting
Set the option board parameters again.
12.3.95 Fault Code 45, ID 444 - Device Added (Different Type)
Cause
A new option board, that you have not used before in the same slot, was put in slot D. No parameter settings are saved.
Danfoss A/S © 2023.08
Fault Tracing
AB298035655957en-000201 / DPD01083 | 311