VACON® 100 FLOW
Application Guide
FWD
Output
frequency
Set frequency
0 Hz
Set frequency
REV
Run enable
Ctrl signal 1
Ctrl signal 2
Ctrl signal 3
Keypad stop
button
1
Illustration 43: I/O A Start/Stop Logic = 1
1
Control signal (CS) 1 activates and causes the output
frequency to increase. The motor operates forward.
2
CS2 becomes inactive and causes the frequency to
go to 0.
3
CS1 activates and causes the output frequency to in-
crease again. The motor operates forward.
4
CS3 activates and causes the direction to start to
change (FWD to REV).
5
The Run enable signal is set to OPEN, which causes
the frequency to go to 0. Configure the Run enable
signal with parameter 3.5.1.15.
Selection = 2
Selection number
Selection name
2
CS1 = Forward (edge)
CS2 = Backward (edge)
180 | Danfoss A/S © 2023.08
2
3
4
Description
Use this function to prevent an accidental start. Before starting the motor again,
the start/stop contact must be opened.
5
6
7
8
6
The start attempt with CS1 is not successful, be-
cause the Run enable signal is still OPEN.
7
CS1 activates and the motor accelerates (FWD) to
the set frequency, because the Run enable signal
was set to CLOSED.
8
The STOP button on the keypad is pushed, and the
frequency that is fed to the motor goes to 0. (This
signal only works if the value of P3.2.3 Keypad Stop
Button is Yes.)
9
CS3 activates and causes the motor to start and to
operate in the reverse direction.
10
CS2 becomes inactive and causes the frequency to
go to 0.
Parameter Descriptions
t
9
10
AB298035655957en-000201 / DPD01083