12.3.74 Fault Code 37, ID 361 - Device Changed (Same Type)
Cause
The power unit was replaced by a new one that has the same size. The device is ready to be used. The parameters are available
in the drive.
Troubleshooting
Reset the fault. The drive reboots after you reset the fault.
12.3.75 Fault Code 37, ID 362 - Device Changed (Same Type)
Cause
The option board in slot B was replaced by a new one that you have used before in the same slot. The device is ready to be used.
Troubleshooting
Reset the fault. The drive starts to use the old parameter settings.
12.3.76 Fault Code 37, ID 363 - Device Changed (Same Type)
Cause
The option board in slot C was replaced by a new one that you have used before in the same slot. The device is ready to be
used.
Troubleshooting
Reset the fault. The drive starts to use the old parameter settings.
12.3.77 Fault Code 37, ID 364 - Device Changed (Same Type)
Cause
The option board in slot D was replaced by a new one that you have used before in the same slot. The device is ready to be
used.
Troubleshooting
Reset the fault. The drive starts to use the old parameter settings.
12.3.78 Fault Code 37, ID 365 - Device Changed (Same Type)
Cause
The option board in slot E was replaced by a new one that you have used before in the same slot. The device is ready to be used.
Troubleshooting
Reset the fault. The drive starts to use the old parameter settings.
12.3.79 Fault Code 38, ID 372 - Device Added (Same Type)
Cause
An option board was put into slot B. You have used the option board before in the same slot.
Troubleshooting
The device is ready for use. The drive starts to use the old parameter settings.
12.3.80 Fault Code 38, ID 373 - Device Added (Same Type)
Cause
An option board was put into slot C. You have used the option board before in the same slot.
Troubleshooting
The device is ready for use. The drive starts to use the old parameter settings.
12.3.81 Fault Code 38, ID 374 - Device Added (Same Type)
Cause
An option board was put into slot D. You have used the option board before in the same slot.
Danfoss A/S © 2023.08
Fault Tracing
AB298035655957en-000201 / DPD01083 | 309