VACON® 100 FLOW
Application Guide
12.3.74 Fault Code 37, ID 361 - Device Changed (Same Type)
Cause
•
The power unit was replaced by a new one that has the same size. The device is ready to be used. The parameters are available
in the drive.
Troubleshooting
•
Reset the fault. The drive reboots after you reset the fault.
12.3.75 Fault Code 37, ID 362 - Device Changed (Same Type)
Cause
•
The option board in slot B was replaced by a new one that you have used before in the same slot. The device is ready to be used.
Troubleshooting
•
Reset the fault. The drive starts to use the old parameter settings.
12.3.76 Fault Code 37, ID 363 - Device Changed (Same Type)
Cause
•
The option board in slot C was replaced by a new one that you have used before in the same slot. The device is ready to be
used.
Troubleshooting
•
Reset the fault. The drive starts to use the old parameter settings.
12.3.77 Fault Code 37, ID 364 - Device Changed (Same Type)
Cause
•
The option board in slot D was replaced by a new one that you have used before in the same slot. The device is ready to be
used.
Troubleshooting
•
Reset the fault. The drive starts to use the old parameter settings.
12.3.78 Fault Code 37, ID 365 - Device Changed (Same Type)
Cause
•
The option board in slot E was replaced by a new one that you have used before in the same slot. The device is ready to be used.
Troubleshooting
•
Reset the fault. The drive starts to use the old parameter settings.
12.3.79 Fault Code 38, ID 372 - Device Added (Same Type)
Cause
•
An option board was put into slot B. You have used the option board before in the same slot.
Troubleshooting
•
The device is ready for use. The drive starts to use the old parameter settings.
12.3.80 Fault Code 38, ID 373 - Device Added (Same Type)
Cause
•
An option board was put into slot C. You have used the option board before in the same slot.
Troubleshooting
•
The device is ready for use. The drive starts to use the old parameter settings.
12.3.81 Fault Code 38, ID 374 - Device Added (Same Type)
Cause
•
An option board was put into slot D. You have used the option board before in the same slot.