VACON® 100 FLOW
Application Guide
12.3.43 Fault Code 14, ID 138 - AC Drive Overtemperature (Fault)
Cause
•
Output filter temperature is too high.
Troubleshooting
•
Check the motor cables and the motor.
•
Check the correct amount and flow of cooling air.
•
Check the ambient temperature.
12.3.44 Fault Code 14, ID 139 - AC Drive Overtemperature (Fault)
Cause
•
Brake chopper temperature is too high.
Troubleshooting
•
Check the correct amount and flow of cooling air.
•
Check the heat sink of the brake chopper for dust.
•
Check the ambient temperature.
12.3.45 Fault Code 15, ID 140 - Motor Stall
Cause
•
The motor stalled.
Troubleshooting
•
Check the motor and the load.
12.3.46 Fault Code 16, ID 150 - Motor Overtemperature
Cause
•
There is too heavy a load on the motor.
Troubleshooting
•
Decrease the motor load. If there is no motor overload, check the motor thermal protection parameters (parameter group 3.9
Protections).
12.3.47 Fault Code 17, ID 160 - Motor Underload
Cause
•
There is not a sufficient load on the motor.
Troubleshooting
•
Check the load.
•
Check the parameters.
•
Check the dU/dt and sine wave filters.
12.3.48 Fault Code 18, ID 170 - Unbalance
Cause
•
The current is unbalanced between power units.
Troubleshooting
•
Check the motor cables and connections.
•
Check the output filters (dU/dt filter, sine filter).
•
Reset the fault and restart the drive.
•
If the fault occurs again, ask for instructions from your nearest service center or distributor. Report carefully all the used soft-
ware, application and options.
304 | Danfoss A/S © 2023.08
Fault Tracing
AB298035655957en-000201 / DPD01083