11.24.9.27 (ID 3573) Load Warning S1 High
Location in the menu: P3.24.5.2.3
Use this parameter to set the threshold value for computing the warning 1 high notification threshold. Threshold value range varies
based on warning mode selection. This limit is not used when value is zero.
11.24.9.28 (ID 3574) Load Warning S1 Delay
Location in the menu: P3.24.5.2.4
Use this parameter to define how long time the actual value must be above the warning S1 notification level to trigger the warning
S1. This level is not used when delay is zero.
11.24.9.29 (ID 3575) Load Warning S2 Mode
Location in the menu: P3.24.5.2.5
Use this parameter to select the warning S2 mode which is used for calculating warning S2 notification threshold.
Selection number
Selection name
0
Absolute
1
Offset
2
Factor
11.24.9.30 (ID 3576) Load Warning S2 High
Location in the menu: P3.24.5.2.7
Use this parameter to set the threshold value for computing the warning 2 high notification threshold. Threshold value range varies
based on warning mode selection. This limit is not used when value is zero.
11.24.9.31 (ID 3577) Load Warning S2 Delay
Location in the menu: P3.24.5.2.8
Use this parameter to define how long time the actual value must be above the warning S2 notification level to trigger the warning
S2. This level is not used when delay is zero.
11.24.9.32 (ID 3578) Load Alarm/Fault Mode
Location in the menu: P3.24.5.2.9
Use this parameter to select the alarm/fault mode which is used for calculating alarm/fault notification threshold.
Selection number
Selection name
0
Absolute
1
Offset
2
Factor
11.24.9.33 (ID 3579) Load Alarm/Fault High
Location in the menu: P3.24.5.2.11
Use this parameter to set the threshold value for computing the alarm/fault high notification threshold. Threshold value range var-
ies based on warning mode selection. This limit is not used when value is zero.
11.24.9.34 (ID 3580) Load Alarm/Fault Delay
Location in the menu: P3.24.5.2.12
Use this parameter to define how long time the actual value must be above the alarm/fault notification level to trigger the alarm/
fault. This level is not used when delay is zero.
288 | Danfoss A/S © 2023.08
Description
Absolute value is considered as threshold
Calculates threshold as sum of the computed baseline data and the offset values
Calculates threshold as baseline data factor
Description
Absolute value is considered as threshold
Calculates threshold as sum of the computed baseline data and the offset values
Calculates threshold as baseline data factor
Parameter Descriptions
AB298035655957en-000201 / DPD01083