VACON® 100 FLOW
Application Guide

6.7 Group 3.7: Prohibit Frequencies

Table 55: Prohibit Frequencies Parameters
Index
Parameter
P3.7.1
Prohibit Frequency Range 1 Low Limit
P3.7.2
Prohibit Frequency Range 1 High Limit
P3.7.3
Prohibit Frequency Range 2 Low Limit
P3.7.4
Prohibit Frequency Range 2 High Limit
P3.7.5
Prohibit Frequency Range 3 Low Limit
P3.7.6
Prohibit Frequency Range 3 High Limit
P3.7.7
Ramp Time Factor

6.8 Group 3.8 Supervisions

Table 56: Supervision Settings
Index
Parameter
P3.8.1
Supervision #1 Item Selection
P3.8.2
Supervision #1 Mode
P3.8.3
Supervision #1 Limit
P3.8.4
Supervision #1 Limit Hysteresis
P3.8.5
Supervision #2 Item Selection
104 | Danfoss A/S © 2023.08
Min
Max
-1.00
320.00
0.00
320.00
0.00
320.00
0.00
320.00
0.00
320.00
0.00
320.00
0.1
10.0
Min
Max
Unit
0
17
0
2
-50.00
50.00
Varies
0.00
50.00
Varies
0
17
Unit
Default
ID
Hz
0.00
509
Hz
0.00
510
Hz
0.00
511
Hz
0.00
512
Hz
0.00
513
Hz
0.00
514
Times
1.0
518
Default
ID
Description
0
1431
0 = Output frequency
1 = Frequency reference
2 = Motor current
3 = Motor torque
4 = Motor power
5 = DC link voltage
6 = Analog input 1
7 = Analog input 2
8 = Analog input 3
9 = Analog input 4
10 = Analog input 5
11 = Analog input 6
12 = Temperature input 1
13 = Temperature input 2
14 = Temperature input 3
15 = Temperature input 4
16 = Temperature input 5
17 = Temperature input 6
0
1432
0 = Not used
1 = Low limit supervision
2 = High limit supervision
25.00
1433
5.00
1434
1
1435
See P3.8.1
AB298035655957en-000201 / DPD01083
Parameters Menu
Description
0 = Not used
0 = Not used
0 = Not used
0 = Not used
0 = Not used
0 = Not used