Information for OEM and Setup users | Commissioning
Parameter
Standstill monitoring for non-
controlled axes
Linear position tolerance for
active standstill monitoring
Radial position tolerance for
active standstill monitoring
HEIDENHAIN | POSITIP 8000 | Operating Instructions Turning | 03/2022
Explanation
Selection of whether standstill monitoring is to be used
Settings:
ON: Monitoring is activated; during active access of an axis to
the central drive, all other axes that are configured as central-
drive axis are monitored for standstill. If the position tolerance
is exceeded, the central drive is switched off with a corre-
sponding error message
OFF: Monitoring is deactivated; during access of an axis to the
central drive, all other axes can be moved freely
Default value: OFF
Starting from this threshold value, movement of a noncontrolled
linear axis is assumed and the central drive is stopped with a
corresponding error message
Setting range: 0.005 mm ... 2.000 mm
Default value: 0.05 mm
Starting from this threshold value, movement of a noncontrolled
rotary axis is assumed and the central drive is stopped with a
corresponding error message
Setting range: 0.005 ° ... 45.000 °
Default value: 0.5 °