FusionModule2000 Smart Modular Data Center
Maintenance Guide
Step 4 Install the smoke detector on the control skylight.
Step 5 Verify that the smoke detector function is normal.
----End
5.4.9 Replacing Cabinet Temperature Sensors
Impact on the System
The cabinet temperature cannot be detected during replacement.
Preparations
Procedure
Step 1 Remove the temperature sensor cables from the rack environment unit.
Step 2 Remove the fasteners that secure the temperature sensors and remove the sensors.
Step 3 Secure the new temperature sensors to the original positions in the cabinet using fasteners,
and connect their cables to the rack environment unit.
Issue 04 (2020-01-03)
Tools: ESD wrist strap, ESD gloves
Material: cabinet temperature sensor
Copyright © Huawei Technologies Co., Ltd.
5 Parts Replacement
91