Horizontal Communication Via Goose For Interlocking Gooseintlkrcv; Setting Guidelines; Generic Communication Function For Single Point Indication Spgapc, Sp16Gapc; Application - ABB RELION 650 Series Applications Manual

Transformer protection version 2.1
Hide thumbs Also See for RELION 650 Series:
Table of Contents

Advertisement

1MRK 504 158-UEN A
15.2.2
Horizontal communication via GOOSE for interlocking
GOOSEINTLKRCV
Table 32:
GOOSEINTLKRCV Non group settings (basic)
Name
Values (Range)
Operation
15.2.3

Setting guidelines

There are two settings related to the IEC 61850–8–1 protocol:
Operation User can set IEC 61850 communication to On or Off .
GOOSE has to be set to the Ethernet link where GOOSE traffic shall be send and received.
15.2.4
Generic communication function for Single Point indication
SPGAPC, SP16GAPC
15.2.4.1

Application

Generic communication function for Single Point Value (SPGAPC) function is used to send one
single logical output to other systems or equipment in the substation. It has one visible input,
that should be connected in ACT tool.
15.2.4.2
Setting guidelines
There are no settings available for the user for SPGAPC.
15.2.5

Generic communication function for Measured Value MVGAPC

15.2.5.1
Application
Generic communication function for Measured Value MVGAPC function is used to send the
instantaneous value of an analog signal to other systems or equipment in the substation. It
can also be used inside the same IED, to attach a RANGE aspect to an analog value and to
permit measurement supervision on that value.
15.2.5.2
Setting guidelines
The settings available for Generic communication function for Measured Value (MVGAPC)
function allows the user to choose a deadband and a zero deadband for the monitored signal.
Values within the zero deadband are considered as zero.
The high and low limit settings provides limits for the high-high-, high, normal, low and low-
low ranges of the measured value. The actual range of the measured value is shown on the
range output of MVGAPC function block. When a Measured value expander block (RANGE_XP)
Application manual
Unit
Off
-
On
Step
Default
-
Off
Station communication
Description
Operation Off/On
Section 15
SEMOD173197-1 v2
PID-415-SETTINGS v5
SEMOD55317-5 v6
SEMOD55999-1 v4
SEMOD55350-5 v7
SEMOD55376-5 v5
SEMOD55402-1 v3
SEMOD55872-5 v9
SEMOD55424-5 v5
229

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ret650

Table of Contents