Section 7
IEC 61850 communication engineering
7.1.2
7.1.2.1
102

IEC 61850 interface in the protection relay

FBs
FBs
GOOSE
GOOSE
Receive
LN
Receive
LN
GOOSE
GOOSE
Send
Send
FB
FBs
AFL
with
monitoring
LN
only
part
FB
AFL
FBs
LN
with
part
monitoring
and
commands
FB
AFL
LN
part
GUID-34A94216-83C6-4F05-8F12-E9BCCA2A5CF7 V1 EN
Figure 75:
IEC 61850: Communication interface principle
IEC 61850 provides a method for identifying all signals that belong to a function.
These signals are identified through the logical nodes representing the functions. All
signal information for commands and monitoring are available in logical nodes.
Whenever a function block is instantiated in the Application Configuration tool,
PCM600 automatically generates the corresponding logical node data.

GOOSE data exchange

The IEC 61850 protocol supports a method to directly exchange data between two or
more IEDs. This method is described in the IEC 61850–7–2 clause 15. The concept is
based on sending multicast telegrams over the Ethernet. Whoever needs the
information detects the telegram by its destination address and will read the telegram
and deals with it. The telegrams are multicast sent and not acknowledged by the
receiver.
1MRS756800 F
GOOSE
Receive
GOOSE
Send
Commands
Event
handler
Event
queue
IEC08000364.vsd
630 series