Goose - ABB Relion Applications Manual

Voltage protection and control
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRS758335 B
3.4.4.4
REU611
Application Manual

GOOSE

There are 20 GOOSERCV_BIN functions in the configuration. Each
GOOSERVC_BIN function can be connected to one received binary GOOSE signal.
The signal connection can be configured in PCM600.
GOOSERCV_BIN instances 0 and 1 are used for blocking protection functions.
Signals from these two GOOSERCV_BINs are connected to ISWGAPC9.
ISWGAPC9 is used to configure which protection function block is blocked.
GOOSERCV_BIN instances 2 and 3 are used for tripping from GOOSE. Signals
from these two GOOSERCV_BINs are connected to TRPPTRC1 and
TRPPTRC2 trip.
GOOSERCV_BIN instances 4 to 19 are used for blocking circuit breaker
operation. Signals from these 16 GOOSERCV_BINs are connected to
ISWGAPC10. ISWGAPC10 is used to configure the GOOSE input signal to
block the circuit breaker open or close operation.
GOOSERCV_BIN:0
GOOSERCV_BIN:1
GOOSERCV_BIN:2
GOOSERCV_BIN:3
GOOSERCV_BIN:4
GOOSERCV_BIN:5
GOOSERCV_BIN:19
GUID-4388A3EC-3534-4618-A0CD-47147FD0591E V1 EN
Figure 52:
GOOSE overview
ISWGAPC9
ISWGAPC9 is used to configure which protection functions can be blocked by the
received GOOSE signals. ISWGAPC9 inputs are received GOOSE signals from
REU611 standardized configuration
GOOSE Blcoking
OR
ISWGAPC9
GOOSE
External Trip
OR
GOOSE Block CB
OR
ISWGAPC10
Section 3
PHPTOV1_BLOCK
PHPTOV2_BLOCK
PHPTOV3_BLOCK
PHPTUV1_BLOCK
PHPTUV2_BLOCK
PHPTUV3_BLOCK
ROVPTOV1_BLOCK
ROVPTOV2_BLOCK
ROVPTOV3_BLOCK
FRPFRQ1_BLOCK
FRPFRQ2_BLOCK
NSPTOV1_BLOCK
NSPTOV2_BLOCK
PSPTUV1_BLOCK
PSPTUV2_BLOCK
CBXCBR1_BLK_CLOSE
CBXCBR1_BLK_OPEN
67