9.4 Tuning-less Function

9.4.3 Troubleshooting Alarms

2.
Click the
level setting to increase the response. Decrease the response level setting to suppress
vibration.
The default response level setting is 4.
Response Level Setting
3.
Click the Completed Button.
The adjustment results will be saved in the SERVOPACK.
Important
 Related Parameters
 Tuning-less Rigidity Level
If you use tuning-less type 1 or 2 (Pn14F = n.0 or n.1), set the tuning-less level to
between 0 and 4 (Pn170 = n.0 to n.4). Do not set the tuning-less level to between
5 and 7 (Pn170 = n.5 to n.7).
Pn170
(2170h)
 Tuning-less Load Level
Pn170
(2170h)
9.4.3

Troubleshooting Alarms

An A.521 alarm (Autotuning Alarm) will occur if a resonant sound occurs or if excessive vibra-
tion occurs during position control. If an alarm occurs, implement the following measures.
• Resonant Sound
Decrease the setting of Pn170 = n.X or the setting of Pn170 = n.X.
• Excessive Vibration during Position Control
Increase the setting of Pn170 = n.X or decrease the setting of Pn170 = n.X.
9-14
or
Button to adjust the response level setting. Increase the response
7
Response level: High
6
5
4 (default setting)
3
2
1
0
Response level: Low
Reset the tuning-less level to the default setting when removing the Servomotor from the
machine. The Servomotor may vibrate if the tuning-less level is not reset and the servo is turned
ON when the Servomotor has been removed from the machine.
Parameter

n.
0
Tuning-less rigidity level 0 (low rigidity)

n.
1
Tuning-less rigidity level 1

n.
2
Tuning-less rigidity level 2

n.
3
Tuning-less rigidity level 3

n.
4
Tuning-less rigidity level 4
(default setting)

n.
5
Tuning-less rigidity level 5

n.
6
Tuning-less rigidity level 6

n.
7
Tuning-less rigidity level 7 (high rigidity)
Parameter

n.0
Tuning-less load level 0

n.1
Tuning-less load level 1
(default setting)

n.2
Tuning-less load level 2
Description
You cannot select these levels if tuning-less type 1 or 2
(Pn14F = n.0 or n.1) is used.
Description
Description
Remarks
When Enabled
Classification
Immediately
Setup
When Enabled
Classification
Immediately
Setup