Checking The Calibration Position - ABB IRB 760 Product Manual

Hide thumbs Also See for IRB 760:
Table of Contents

Advertisement

5.6 Checking the calibration position

Introduction
Check the calibration position before beginning any programming of the robot
system. This may be done:
Using a MoveAbsJ instruction
Use this procedure to create a program that runs all the robot axes to their zero
position.
1
2
3
4
5
6
Using the jogging window
Use this procedure to jog the robot to the zero position of all axes.
1
2
3
4
5
3HAC039838-001 Revision: C
Using a MoveAbsJ instruction with argument zero on all axes.
Using the Jogging window on the FlexPendant.
Action
On ABB menu tap Program editor.
Create a new program.
Use MoveAbsJ in the Motion&Proc menu.
Create the following program:
MoveAbsJ [[0,0,0,0,0,0],
[9E9,9E9,9E9,9E9,9E9,9E9]]
\NoEOffs, v1000, z50, Tool0
Run the program in manual mode.
Check that the calibration marks for the axes align
correctly. If they do not, update the revolution
counters.
Action
On the ABB menu, tap Jogging.
Tap Motion mode to select group of axes
to jog.
Tap to select the axis to jog, axis 1, 2, or
3.
Manually run the robots axes to a position
where the axis position value read on the
FlexPendant, is equal to zero.
Check that the calibration marks for the
axes align correctly. If they do not, update
the revolution counters!
© Copyright 2013 ABB. All rights reserved.
5 Calibration information
5.6 Checking the calibration position
Note
See
Calibration scale and correct
axis position on page
ing revolution counters on page
Note
See
Calibration scale and correct axis pos-
ition on page
332, and
Updating revolution
counters on page
335.
332, and
Updat-
335.
337

Advertisement

Table of Contents
loading

Table of Contents