6-104
SL-1 NT system upgrades

Converting the SL-1 hardware

553-3001-250 Standard 14.00 August 1996
Continuing with the upgrade will disrupt system operation. Minimal
service can be maintained if a power failure transfer unit (PFTU) is
installed.
Preparing the NT system for upgrade
To prepare an NT system for conversion to an option 61C:
1
Set all shelf circuit breakers to OFF.
2
Set the CAB INP circuit breaker on the QSP43 power control shelf in the
QCA58 cabinet and all other shelf circuit breakers to OFF.
3
Set the AC input circuit breaker on the –48V rectifier in the QCA58
cabinet to OFF.
4
Disconnect all network loop cables connected to QPC414 Network cards
and cables connected to QPC139 SDI cards.
5
Set the ENB/DIS switch on the faceplate of the QPC33 Tape Unit
Interface (TUI) card located in the CPU/MEM shelf to DIS. If equipped
with a mass storage unit, repeat this step for the mass storage unit
interface card.
6
Remove the tape and set the power switch on the faceplate of the tape
unit to OFF or 0. If equipped with a mass storage unit, repeat this step by
removing the disks and turning the MSU power switch to OFF.
7
Disconnect and remove the cable from the faceplate of the QPC33 card
to the tape unit. If equipped with a mass storage unit, disconnect the cable
between the MSU and the MSI or EMSI faceplates.
8
Disconnect cables from the faceplate connectors on cards located in the
CPU/MEM and network shelves.
9
Remove cards from the CPU/MEM shelf and store them in a safe place.
CAUTION