Table 12-24
Group 0 connections on the left I/O panel: NTND94DA cables
Core 0 cable label
CPU0-CNI-8F to
3PE-GRP0/0-J4
CPU0-CNI-8D to
3PE-GRP0/0-J3
22 Mount an A0360683 50-pin adapter at slot J32, pin 1 to the top.
23 Mount an A0369106 9-pin filter adapter at slot J29, pin 1 to the bottom,
using the A0314862 screw lock kit.
24 Mount an A0369106 9-pin filter adapter at slot J33, pin 1 to the bottom,
using the A0314862 screw lock kit.
25 Connect the NTND94DA CNI cables to the inside of the I/O panels as
listed in Table 12-24.
26 Plug an NT1R04AA cable into the adapter on slot J32 and lock the cable
in position using the bail locks:
In Core 0 the cable is labeled CPU0-CC-J3 to JCTR-J11.
In Core 1 the cable is labeled CPU1-CC-J3 to JCTR-J12.
27 Attach an A0314862 screw lock kit to the filter adapter in slot J33. Plug
an NT8D79AD cable into the adapter, and secure it with the screws on
the connector:
In Core 0 the cable is labeled CPU0-CC-J1 to SEC PRI-J1.
In Core 1 the cable is labeled CPU1-CC-J1 to SEC PRI-J2.
28 Attach an A0314862 screw lock kit to the filter adapter in slot J29. Plug
an NT8D79AD cable into the adapter, and secure it with the screws on
the connector:
In Core 0 the cable is labeled CPU0-CC-J2 to PRIM PRI-J1.
In Core 1 the cable is labeled CPU1-CC-J2 to PRIM PRI-J2.
Core 1 cable label
CPU1-CNI-8F to
3PE-GRP0/1-J4
CPU1-CNI-8D to
3PE-GRP0/1-J3
Upgrade system installation Upgrading to Meridian 1 system options
Upgrades to Meridian 1 option 81
I/O slot
J27
J26
12-125
Backplane
connector
8F
8D