Diagnostics Memory Trace Control Word / Trace Stw; Diagnostics Memory Copy Recording File To Memory Card / Copy Diag File; Device Fan Test / Dev Fan Test - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Value:
0:
1:
2:
3:
Dependency:
Refer to: F60061
Note:
The thyristor test function cannot be used when supplying extremely high inductances (e.g. when supplying a field
from armature terminals, supplying solenoids, etc.) and must be de-activated (p50830 = 0).
When SINAMICS DCM are connected in parallel (6 pulse or 12 pulse), thyristor diagnostics
may only be selected at the master. The thyristor diagnostics is then
first carried out at the master, and then automatically at all of the slaves one after the other. If
a defective thyristor is detected at a SINAMICS DCM, then the corresponding
fault message is initiated at this SINAMICS DCM and not at the master where
thyristor diagnostics was started.
p50831

Diagnostics memory trace control word / Trace STW

DC_CTRL
Can be changed: U, T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Sets the trigger resolution for the trace.
Value:
0:
1:
2:
p50832

Diagnostics memory copy recording file to memory card / Copy diag file

DC_CTRL
Can be changed: U, T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Setting for starting the procedure to copy the diagnostics file to the memory card.
Value:
0:
1:
2:
Note:
The value is reset automatically at the end of the copying procedure.
If a diagnostics file is empty, the file written to the memory card will also be empty.
This file will overwrite any existing file on the memory card.
p50833

Device fan test / Dev fan test

DC_CTRL
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Setting to test the device fans.
Value:
0:
1:
Dependency:
Refer to: r53135
Refer to: F60167
Note:
The status of the fans is displayed in binector outputs r53135.8 to 11.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Switched off
After the first ON command
After each ON command
After next ON command
No trigger for start
Start immediately
Start together with STARTER trace
Inactive
Start copying procedure
Copy file into User\Data folder
Stop fan
Start fan
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
2
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
2
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 8052
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 8052
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 8047
Unit selection: -
Expert list: 1
Factory setting
0
525