2 Parameters
2.2 List of parameters
When comparing the topology, the following data is compared in the target and actual topologies:
p9906 = 0: Component type, Order No., Hardware version, Manufacturer, Serial No.
p9906 = 1: Component type, Order No.
p9906 = 2: Component type
p9906 = 3: Component class (e.g. Sensor Module or Motor Module)
p9907

Topology comparison comparison stage of the component number /

Topo_cmpr comp_no
CU_DC, CU_DC_R,
Can be changed: C1(1)
CU_DC_R_S,
Data type: Unsigned8
CU_DC_S
P-Group: Topology
Not for motor type: -
Min
0
Description:
Enters the number of the component where the setting of how the actual topology should be compared to the target
topology should be changed.
Dependency:
Refer to: p9908
p9908
Topology comparison comparison stage of a component / Topo_cmpr 1 comp
CU_DC, CU_DC_R,
Can be changed: C1(1)
CU_DC_R_S,
Data type: Integer16
CU_DC_S
P-Group: Topology
Not for motor type: -
Min
0
Description:
Sets the type of comparison of a component in the target topology with the actual topology.
The comparison is started by setting the required value.
Value:
0:
1:
2:
3:
99:
Dependency:
Refer to: p9907
Note:
The electronic rating plate comprises the following data:
- component type (e.g. "SMC20")
- Order No. (e.g. "6SL3055-0AA0-5BA0")
- manufacturer (e.g. SIEMENS)
- hardware version (e.g. "A")
- Serial No. (e.g. "T-P30050495")
When comparing the topology, the following data is compared in the target and actual topologies:
p9908 = 0: Component type, Order No., Hardware version, Manufacturer, Serial No.
p9908 = 1: Component type, Order No.
p9908 = 2: Component type
p9908 = 3: Component class (e.g. Sensor Module or Motor Module)
p9909

Topology comparison component replacement / Topo_cmpr replace

CU_DC, CU_DC_R,
Can be changed: C1(1)
CU_DC_R_S,
Data type: Unsigned8
CU_DC_S
P-Group: Topology
Not for motor type: -
Min
0
Description:
For p9909 = 1, the serial number and the hardware version of the new replaced component is automatically
transferred from the actual topology into the target topology and then saved in a non-volatile fashion.
362
High: Compares the complete electronic rating plate
Average: Compares the component type and the Order number
Low: Compares the component type
Minimum: Compares the component class
Topology has different comparison stages
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
199
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
99
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
SINAMICS DCM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents