Bi: Topology Switchover Signal Source / Top_Switch S_Src; Bi: Topology Switchover Feedback Signal Source / Top_Sw Fdbk S_Src; Topology Switchover Feedback Signal Stabilization Time; Topology Switchover Feedback Signal Duration - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
Note:
Active faults are signaled at r2139.3 and r3114.10.
p51790

BI: Topology switchover signal source / Top_switch s_src

DC_CTRL
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source to select the required power unit topology.
p51791

BI: Topology switchover feedback signal source / Top_sw fdbk s_src

DC_CTRL
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for the feedback signal of the active power unit topology.
p51792
Topology switchover feedback signal stabilization time / Topo_sw t_stab
DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0 [ms]
Description:
Sets the stabilization time for the feedback signal of the active power unit topology.
p51793
Topology switchover feedback signal duration / Topo_sw fdbk t_sig
DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0 [ms]
Description:
Sets the maximum duration of the power unit topology switchover.
p51794
Topology switchover armature converter mode of operation 2 / Topo_sw mode 2
DC_CTRL
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Sets the mode of operation of the armature converter for power unit topology 2.
Value:
0:
1:
3:
21:
22:
31:
32:
542
Standard mode of operation
Sole power unit 1-phase
Sole power unit 3-phase
12-pulse parallel, firing angle from the master
12-pulse parallel, firing angle master/slave
6-pulse serial, firing angle from the master
6-pulse serial with sequential phase control
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1000 [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
10000 [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
42
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 2
Func. diagram: 9360
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 9360
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 9360
Unit selection: -
Expert list: 1
Factory setting
0 [ms]
Access level: 2
Func. diagram: 9360
Unit selection: -
Expert list: 1
Factory setting
100 [ms]
Access level: 3
Func. diagram: 9360
Unit selection: -
Expert list: 1
Factory setting
0
SINAMICS DCM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents