p50162[0...n]

EMF selection / EMF sel

DC_CTRL
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
1
Description:
Sets the calculation method for the EMF in armature pre-control.
Value:
1:
2:
3:
4:
Note:
If p50162 = 1:
The EMF derived from the measured armature voltage (r52123) is used.
If p50162 = 2:
The EMF for armature current pre-control is calculated from the armature voltage selected with p50193 (the resistive
+ inductive armature voltage drop is subtracted internally).
If p50162 = 3:
The parameter selected with p50193 is used as the EMF for armature current pre-control. This setting also allows a
closed-loop DC link voltage control to be implemented.
If p50162 = 4:
The EMF for the armature precontrol (12-pulse in parallel) is calculated as follows:
r52290 * (r52167/p50119) * p50118
p50163[0...n]

EMF smoothing selection / EMF smoothing sel

DC_CTRL
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Sets the method for filtering the EMF for armature pre-control.
Value:
0:
1:
2:
3:
4:
5:
6:
10:
20:
40:
80:
160:
p50164[0...n]
Closed-loop armature current ctr proportional comp activation / Ia ctr Kp act
DC_CTRL
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Sets activation/de-activation of the proportional component for armature current control.
Value:
0:
1:
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Measured EMF
EMF with Ua from p50193
EMF with EMF from p50193
EMF with EMF from r52167
No filtering
Averaging over last 1 EMF values
Averaging over last 2 EMF values
Averaging over last 3 EMF values
Averaging over last 4 EMF values
Averaging over last 5 EMF values
Averaging over last 6 EMF values
PT1 time constant = 10 ms
PT1 time constant = 20 ms
PT1 time constant = 40 ms
PT1 time constant = 80 ms
PT1 time constant = 160 ms
Deactivated
Activated
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
4
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
160
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
1
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 6852
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 2
Func. diagram: 6852
Unit selection: -
Expert list: 1
Factory setting
6
Access level: 2
Func. diagram: 6855
Unit selection: -
Expert list: 1
Factory setting
1
413

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents