p1140[0...n]
BI: Enable ramp-function generator/inhibit ramp-function generator / RFG enable
DC_CTRL,
Can be changed: T
DC_CTRL_R,
Data type: Unsigned32 / Binary
DC_CTRL_R_S,
P-Group: Setpoints
DC_CTRL_S
Not for motor type: -
Min
-
Description:
Sets the signal source for the command "enable ramp-function generator/inhibit ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 4 (STW1.4).
BI: p1140 = 0 signal:
Inhibits the ramp-function generator (the ramp-function generator output is set to zero).
BI: p1140 = 1 signal:
Ramp-function generator enable.
Dependency:
Refer to: p1141, p1142
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1141[0...n]
BI: Continue ramp-function generator/freeze ramp-function generator / Continue RFG
DC_CTRL,
Can be changed: T
DC_CTRL_R,
Data type: Unsigned32 / Binary
DC_CTRL_R_S,
P-Group: Setpoints
DC_CTRL_S
Not for motor type: -
Min
-
Description:
Sets the signal source for the command "continue ramp-function generator/freeze ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 5 (STW1.5).
BI: p1141 = 0 signal:
Freezes the ramp-function generator.
BI: p1141 = 1 signal:
Continue ramp-function generator.
Dependency:
Refer to: p1140, p1142
Caution:
When "master control from PC" is activated, this binector input is ineffective.
p1142[0...n]

BI: Enable setpoint/inhibit setpoint / Setpoint enable

DC_CTRL,
Can be changed: T
DC_CTRL_R,
Data type: Unsigned32 / Binary
DC_CTRL_R_S,
P-Group: Setpoints
DC_CTRL_S
Not for motor type: -
Min
-
Description:
Sets the signal source for the command "enable setpoint/inhibit setpoint".
For the PROFIdrive profile, this command corresponds to control word 1 bit 6 (STW1.6).
BI: p1142 = 0 signal
Inhibits the setpoint (the ramp-function generator input is set to zero).
BI: p1142 = 1 signal
Setpoint enable.
Dependency:
Refer to: p1140, p1141
Caution:
When "master control from PC" is activated, this binector input is ineffective.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 2580
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 2580
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 2580
Unit selection: -
Expert list: 1
Factory setting
1
121