List Of Parameters; Control Unit Operating Display / Cu Op_Display; Drive Operating Display / Drv Op_Display - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

2 Parameters

2.2 List of parameters

2.2
List of parameters
Product: SINAMICS DC MASTER, Version: 4702900, Language: eng
Objects: CU_DC, CU_DC_R, CU_DC_R_S, CU_DC_S, DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S, TM150, TM15DI_DO, TM31
Product: SINAMICS DC MASTER OA, Version: 1401800, Language: eng
Objects: DC_CTRL
r0002

Control Unit operating display / CU op_display

CU_DC, CU_DC_R,
Can be changed: -
CU_DC_R_S,
Data type: Integer16
CU_DC_S
P-Group: -
Not for motor type: -
Min
0
Description:
Operating display for the Control Unit (CU).
Value:
0:
10:
20:
25:
31:
33:
34:
35:
70:
80:
99:
Notice:
For several missing enable signals, the corresponding value with the highest number is displayed.
r0002

Drive operating display / Drv op_display

DC_CTRL,
Can be changed: -
DC_CTRL_R,
Data type: Integer16
DC_CTRL_R_S,
P-Group: -
DC_CTRL_S
Not for motor type: -
Min
0
Description:
Operating display for the drive.
Value:
0:
1:
2:
9:
10:
11:
12:
13:
14:
15:
16:
17:
18:
19:
20:
21:
22:
30:
31:
32:
33:
34:
35:
40:
41:
42:
28
Operation
Ready
Wait for run-up
Wait for automatic FW update of DRIVE-CLiQ components
Commissioning software download active
Remove/acknowledge topology error
Exit commissioning mode
Carry out first commissioning
Initialization
Reset active
Internal software error
o0.0 No torque direction switched on
o0.1 Torque direction I switched on
o0.2 Torque direction II switched on
o0.9 Wait for enable from master
o1.0 Wait time for brake opening time running
o1.1 Wait for operating enable at terminal 13
o1.2 Wait for operating enable (signal source acc. to p0852)
o1.3 Wait time after withdrawing a jog command running
o1.4 Wait until the field has been reversed
o1.5 Wait for operating enable from the optimization run
o1.6 Wait for withdrawal of the immediate pulse inhibit
o1.7 Wait for SINAMICS DCM connected in parallel in status o0.0
o1.8 Operating state o1.8
o1.9 Operating state o1.9
o2.0 Wait for setpoint
o2.1 Operating state o2.1
o2.2 Operating state o2.2
o3.0 Wait for the thyristor check to be completed
o3.1 Wait for line supply symmetry
o3.2 Wait for a DC contactor to pick up
o3.3 Wait for the feedback signal "main contactor"
o3.4 Operating state o3.4
o3.5 Operating state o3.5
o4.0 Wait for voltage at 1U1, 1V1, 1W1
o4.1 Wait until fuse monitoring signals OK
o4.2 Operating state o4.2
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
99
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
129
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 1
Func. diagram: 2651
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 1
Func. diagram: 2651
Unit selection: -
Expert list: 1
Factory setting
-