Gearbox Factor Motor/Load Revolutions / Grbx_Fact Mot_Rev; Encoder Ssi Error Bit / Enc Ssi Error Bit - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p0433[0...n]

Gearbox factor motor/load revolutions / Grbx_fact mot_rev

DC_CTRL,
Can be changed: C2(4)
DC_CTRL_R,
Data type: Integer16
DC_CTRL_R_S,
DC_CTRL_S
P-Group: Encoder
Not for motor type: -
Min
1
Description:
Sets the motor and load revolutions for the gearbox factor of the encoder evaluation.
The gearbox factor specifies the ratio between the encoder shaft and motor shaft (for motor encoders) or between
the encoder shaft and the load.
Dependency:
This parameter can only be set for p0402 = 9999.
Refer to: p0402, p0410, p0432
Note:
Negative gearbox factors should be implemented with p0410.
p0434[0...n]

Encoder SSI error bit / Enc SSI error bit

DC_CTRL,
Can be changed: C2(4)
DC_CTRL_R,
Data type: Unsigned16
DC_CTRL_R_S,
P-Group: Encoder
DC_CTRL_S
Not for motor type: -
Min
0
Description:
Sets the position and level of the error bit in the SSI protocol.
Notice:
The bit may only be positioned before (p0446) or after (p0448) the absolute value in the SSI protocol.
Note:
Value = dcba
ba: Position of the error bit in the protocol (0 ... 63).
c: Level (0: Low level, 1: High level).
d: Status of the evaluation (0: Off, 1: On with 1 error bit, 2: On with 2 error bits ... 9: On with 9 error bits).
For several error error bits, the following applies:
- the position specified under ba and the additional bits are assigned increasing consecutively.
- the level set under c applies to all error bits.
Example:
p0434 = 1013
--> The evaluation is switched in and the error bit is at position 13 with a low level.
p0434 = 1113
--> The evaluation is switched in and the error bit is at position 13 with a high level.
p0435[0...n]
Encoder SSI alarm bit / Enc SSI alarm bit
DC_CTRL,
Can be changed: C2(4)
DC_CTRL_R,
Data type: Unsigned16
DC_CTRL_R_S,
P-Group: Encoder
DC_CTRL_S
Not for motor type: -
Min
0
Description:
Sets the position and level of the alarm bit in the SSI protocol.
Notice:
The bit may only be positioned before (p0446) or after (p0448) the absolute value in the SSI protocol.
Note:
Value = dcba
ba: Position of the alarm bit in protocol (0 ... 63).
c: Level (0: Low level, 1: High level).
d: State of the evaluation (0: Off, 1: On).
74
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
10000
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
65535
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
65535
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 3
Func. diagram: 4704, 4710,
4711
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0