2 Parameters
2.2 List of parameters
p50375[0...n]

Messages for reference speed OFF delay / Ref_speed t_OFF

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.0 [s]
Description:
Sets the OFF delay for the "Reference speed reached" message.
Dependency:
Refer to: p50373, p50374, p50592, r53025
p50376[0...n]
Messages for setpoint/actual value deviation 2 threshold / Set/act 2 thresh
DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.00 [%]
Description:
Sets the threshold for the "Setpoint/actual value deviation 2 reached" message.
Dependency:
Refer to: p50377, p50378, p50596, p50597, r53025
Note:
The "Setpoint/actual value deviation 2 reached" message is available as follows:
- r53025.2 (not inverted)
- r53025.3 (inverted)
p50377[0...n]
Messages for setpoint/actual value deviation 2 hysteresis / Set/act 2 hyst
DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.00 [%]
Description:
Sets the hysteresis for the "Setpoint/actual value deviation 2 reached" message.
The message is triggered when the threshold is overshot.
Once the value falls below the threshold minus the hysteresis, the message is withdrawn.
Dependency:
Refer to: p50376, p50378, p50596, p50597, r53025
p50378[0...n]
Messages for setpoint/actual value deviation 2 OFF delay / Set/act 2 t_OFF
DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.0 [s]
Description:
Sets the OFF delay for the "Setpoint/actual value deviation 2 reached" message.
Dependency:
Refer to: p50376, p50377, p50596, p50597, r53025
448
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
100.0 [s]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: PERCENT
Max
200.00 [%]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: PERCENT
Max
200.00 [%]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
100.0 [s]
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 2
Func. diagram: 8020
Unit selection: -
Expert list: 1
Factory setting
3.0 [s]
Access level: 2
Func. diagram: 8020
Unit selection: -
Expert list: 1
Factory setting
3.00 [%]
Access level: 2
Func. diagram: 8020
Unit selection: -
Expert list: 1
Factory setting
1.00 [%]
Access level: 2
Func. diagram: 8020
Unit selection: -
Expert list: 1
Factory setting
3.0 [s]