2 Parameters
2.2 List of parameters
Note:
OA: Open Architecture (OA application)
r4976

OA invalid identifier total length / OA inv ID tot_lgth

CU_DC, CU_DC_R,
Can be changed: -
CU_DC_R_S,
Data type: Unsigned16
CU_DC_S
P-Group: OEM range
Not for motor type: -
Min
-
Description:
Displays the total length of the IDs of all the invalid OA applications installed on the memory card/device memory.
Dependency:
Refer to: r4975, r4978, r4979
Note:
The identifier of an invalid OA application comprises a maximum of 8 characters plus separator.
r4978[0...n]

OA invalid identifier / OA inv ID

CU_DC, CU_DC_R,
Can be changed: -
CU_DC_R_S,
Data type: Unsigned8
CU_DC_S
P-Group: OEM range
Not for motor type: -
Min
-
Description:
Displays the IDs of all the invalid OA applications installed on the memory card/device memory.
r4978[0...8]: Identifier of invalid OA application 1
r4978[9...17]: Identifier of invalid OA application 2, ...
Dependency:
Refer to: r4975, r4976, r4979
Notice:
If there is no invalid OA application, then it is not possible to access an index.
r4979[0...n]

OA invalid error code / OA inv error code

CU_DC, CU_DC_R,
Can be changed: -
CU_DC_R_S,
Data type: Unsigned32
CU_DC_S
P-Group: OEM range
Not for motor type: -
Min
-
Description:
Displays the error code of the invalid OA applications installed on the memory card/device memory.
r4979[0]: Fault value of OA application 1
r4979[1]: Fault value of OA application 2, ...
Dependency:
Refer to: r4975, r4976, r4978
Notice:
If there is no invalid OA application, then it is not possible to access an index.
Note:
The value in the error code must be interpreted in binary form. The bits have the following meaning:
Bit 0: Incompatible OA interface version.
Bit 1: OA application could not be loaded.
Bit 2: Incorrect description files.
Bit 3: OA application does not define a CPU type.
Bit 4: OA application for this device not supported (incorrect CPU type).
Bit 5: OA application for this device not supported (incorrect type ID).
Bit 6: Incorrect description files (Const/Startup incompatible).
286
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: r4976
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: r4975
Unit group: -
Scaling: -
Max
-
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-