[6] = Temperature channel 6
[7] = Temperature channel 7
[8] = Temperature channel 8
[9] = Temperature channel 9
[10] = Temperature channel 10
[11] = Temperature channel 11
Dependency:
Refer to: p4102, p4103, r4104, r4105
Note:
The following applies for a corresponding alarm:
- Remains until the temperature actual value (r4105[x]) reaches or falls below the threshold value (p4102[2x] -
hysteresis (p4118[x]).
The following applies for a corresponding fault:
- Remains until the temperature actual value (r4105[x]) reaches or falls below the threshold value (p4102[2x+1]) -
hysteresis (p4118[x]) and the fault has been acknowledged.
p4119[0...11]

TM150 activate/deactivate smoothing / TM150 smooth act

TM150
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Setting to activate/deactivate the filter to smooth the temperature signal for the Terminal Module 150 (TM150).
The smoothing is realized with a 1st order lowpass filter
The effective smoothing time constant depends on the number of channels that are simultaneously active and is
displayed in r4120.
Value:
0:
1:
Index:
[0] = Temperature channel 0
[1] = Temperature channel 1
[2] = Temperature channel 2
[3] = Temperature channel 3
[4] = Temperature channel 4
[5] = Temperature channel 5
[6] = Temperature channel 6
[7] = Temperature channel 7
[8] = Temperature channel 8
[9] = Temperature channel 9
[10] = Temperature channel 10
[11] = Temperature channel 11
Dependency:
Refer to: r4120
r4120
TM150 temperature filter time constant / TM150 temp_filt T
TM150
Can be changed: -
Data type: Unsigned16
P-Group: -
Not for motor type: -
Min
- [ms]
Description:
Displays the smoothing time constant for the temperature filter for Terminal Module 150 (TM150).
Dependency:
Refer to: r4105, p4111, r4112, r4113
Note:
The time constant lies in the range from 80 to 1000 ms and depends on the number of channels that are
simultaneously active.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Filter deactivated
Filter activated
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
- [ms]
2 Parameters
2.2 List of parameters
Access level: 1
Func. diagram: 9626, 9627
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: 9626, 9627
Unit selection: -
Expert list: 1
Factory setting
- [ms]
249